Reovib mfs 268 сброс ошибки

Reo Elektronik REOVIB MFS 268 User Manual

  • Contents

  • Table of Contents

  • Bookmarks

Quick Links

REOVIB

Control Equipment for the Vibratory Feeder Industry

MFS 268

Frequency Converter for Vibratory Feeders

UL / CSA — Version

268_UL-CSA_ANL_EN_47-13.DOC

21.11.2013

loading

Related Manuals for Reo Elektronik REOVIB MFS 268

Summary of Contents for Reo Elektronik REOVIB MFS 268

  • Page 1
    REOVIB Control Equipment for the Vibratory Feeder Industry MFS 268 Frequency Converter for Vibratory Feeders UL / CSA — Version 268_UL-CSA_ANL_EN_47-13.DOC 21.11.2013…
  • Page 2: Technical Safety Instructions For The User

    The units described herein are electrical controllers for installation in industrial plant. They are designed for controlling vibratory feeders. For use in NFPA 79 Applications only Adapters providing field wiring means are available from REO ELEKTRONIK AG. Refer to REO ELEKTRONIK AG.

  • Page 3: Table Of Contents

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK Contents Technical safety instructions for the user ………………… 1 1.0 General …………………………3 2.0 Function …………………………3 2.1 Track control ……………………….4 2.2 Operating with two speeds (2 set points for coarse/fine switching) ………… 4 2.3 Control inputs and output ……………………

  • Page 4: General

    ELEKTRONIK 1.0 General The REOVIB MFS 268 range comprises special, adaptable controllers for use with vibratory feeders. The units generate an output frequency, to drive feeders, that is independent of mains frequency and so exact tuning with springs is not necessary. The feeders also run quieter because of the sinusoidal output signal.

  • Page 5: Track Control

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 2.1 Track control output switched ON and OFF Sensor from a track component sensor, using internal, adjustable time delays (ton Feeder and toff). The queue of components rises above and drops below the track sensor…

  • Page 6: Output Status Relay

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 2.3.4 Output status relay Status-Relay contact 250 V/1 A (changeover). Relay closes when the feeder is running – the relay opens when there is no enable signal or a fault displayed. 2.3.5 Time-Out output 24 VDC «time Out»…

  • Page 7: Technical Data

    For use in NFPA 79 Applications only E217179 Adapters providing field wiring means are available from REO ELEKTRONIK AG. Refer to REO ELEKTRONIK AG. 6.0 Declaration of Conformity We declare that these products conform with the following standards: EN 61000-6-4 and EN 61000-6-2 in accordance with the regulations of guidelines 2004/108/EC.

  • Page 8: Settings

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 7.0 Settings After checking the correct operation of the controller in conjunction with the vibratory feed system it is advisable to restrict the user to feeder throughput settings only. Setting the feeder throughput: Press the P key twice and adjust the throughput with the cursor keys (Code C.

  • Page 9: Control Elements

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 8.0 Control elements 8.1 Settings The six buttons and a LED display found in the front panel, are used for operating and setting up the unit. All operating methods and adjustable Display parameters can be set up through this panel.

  • Page 10: Commissioning

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 9.0 Commissioning 9.1 Assembling position Please fasten the devices on a vibration-free underground and take care for sufficient air circulation. 9.2 Preliminary steps • Check that the unit is correct for the local mains supply (rating plate information) and that it is correct- ly rated for the feed system.

  • Page 11: Putting The Equipment Into Operation

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 9.3 Putting the equipment into operation 1. Establish the vibrating frequency. 2. Establish the power of the feed system (maximum permissible current draw). For a new feeder where settings are unknown: (see also comments below) Without connecting the feeder, select parameter FAC in menu C210 (reset factory settings), press the cursor key to reset (SAFE) and press the P key to leave the menu.

  • Page 12: Setting Instructions

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 10.0 Setting Instructions 10.1 User adjustment of throughput Code C. 000 Feeder amplitude set point 0…100 % Running mode A further set point code can be found under C002 (for use in coarse/fine operation) Feeder amplitude set point 0…100 %…

  • Page 13: Track Control

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 10.2.2 Track control Code C. 167, 007 On time delay 0…60 sec. Off time delay 0…60 sec. 0 = No sensor inverting I = Sensor inverting 0 = Sensor time out not active I = Sensor time out active E.

  • Page 14: Pulse Feed

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 10.2.5 Pulse feed Code C. 004, 064 HOP. = 0 = continuous duty HOP. = I = pulse feed On time delay [sec.] Off time delay [sec.] Invert hopper sensor (not active) Running mode 10.2.6 Regulation mode…

  • Page 15: Instructions For Using Regulation Mode

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 10.2.6.1 Instructions for using regulation mode • An accelerometer e.g. SW 70 must be fitted to the vibratory feeder in order to run in regulation mode. The accelerometer should have a frequency range corresponding to that of the feeder.

  • Page 16
    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK In regulation mode the magnitude of the output signal has a direct affect on the maximum ampli- tude of the feeder. On bowl feeders it is advisable to fit the sensor as near as possible to the outside diameter and in this…
  • Page 17: Relationship Between Acceleration And Amplitude

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 10.2.6.3 Relationship between acceleration and amplitude The sensor measures the momentary acceleration of the feeder. It generates a sinusoidal output voltage signal. The acceleration gets higher as the frequency increases. The sensor signal is greater for a higher frequency and lower amplitude than for a low frequency with a higher amplitude.

  • Page 18: Optimisating Controller In Regulation Mode

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 10.2.6.6 Optimisating controller in regulation mode Setting the control range 1. In Menu C. 096 set parameter P (Max Limit) to 50 % 2. Set A (Feeder throughput) to 100% 3. Increase limit P from 50% until the required maximum feeder throughput is achieved The full set point adjustment range of 0…100% can now be used…

  • Page 19: Display Actual Current And Frequency

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 10.2.7 Display actual current and frequency Code C. 040 Actual current (display only) Actual frequency (display only) Running mode 10.2.8 Save selected parameters Code C. 143 Choose user parameter set Save new parameters Running mode 10.2.9 Recall user or factory settings…

  • Page 20: Error Messages / Error Reset

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 11.0 Error messages / ERROR reset Errors are indicated by an alternating code and ERROR display Overload limit Output level exceeded e.g. incorrect frequency setting, coil air- gap to wide. Short circuit trip Faulty coil, short circuit or defective cable..

  • Page 21: Connections For Enclosed Construction (Ip 54): 6-8 A Units

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 12.0 Connections for enclosed construction (IP 54): 6-8 A Units Internal connections When a potentiometer is connected parameter POT must be set to I in Menu C003. Status- relay 1 2 3 4…

  • Page 22: Connections For Enclosed Construction (Ip 54): 12 A Units

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 12.1 Connections for enclosed construction (IP 54): 12 A Units Internal connections Status relay Time out +24 V Air valve +24 V +24 V Accelerometer SW… INPUT Set point (external) +10V 0(4)…20mA 0…10V…

  • Page 23: Connections For Enclosed Construction (Ip 54): 16 A Units

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 12.2 Connections for enclosed construction (IP 54): 16 A Units Internal connections Status relay Time out +24 V Air valve +24 V +24 V Accelerometer SW… INPUT Set point (external) +10V 0(4)…20mA 0…10V…

  • Page 24: Connections For Panel Mounting Construction (Ip 20): 3 A, 6 A, 8 A

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 13.0 Connections for panel mounting construction (IP 20): 3 A, 6 A, 8 A REOVIB MFS268 Material-Sensor +24V Enable 12…24V, DC Set point 0…10V 0(4)…20mA R=500 OHM black External INPUT orange SW… + 24V…

  • Page 25: Connections For Panel Mounting Construction (Ip 20): 16A

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 13.1 Connections for panel mounting construction (IP 20): 16A line choke Mains L, N, PE / 115V/230V, 50/60HZ Material sensor +24V Enable 12…24V, DC Set point 0(4)…20mA 0…10V SPEED +10V black orange INPUT Accelerometer SW…

  • Page 26: Dimensions For 3 A, 6 A, 8 A Units

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 14.0 Dimensions for 3 A, 6 A, 8 A Units Enclosed construction, (IP 54) Ø5,0 REOVIB MFS 268 SPEED www.reo.de Ø5,0 Panel mounting construction, (IP 20) Ø 5,0 Ø 5,0 REOVIB MFS268 REOVIB MFS268 Ø…

  • Page 27: Dimensions Of Enclosed Construction (Ip 54) 12 A

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 14.1 Dimensions of enclosed construction (IP 54) 12 A Ø5,0 REOVIB MFS 268 SPEED www.reo.de Ø5,0 14.2 Dimensions of enclosed construction (IP 54) 16 A Ø5,0 REOVIB MFS 268 SPEED www.reo.de Ø5,0…

  • Page 28: Dimensions Of Panel Mounting Construction (Ip 20) 16 A

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 14.3 Dimensions of Panel mounting construction (IP 20) 16 A Ø5,0 SPEED +10V Ø5,0…

  • Page 29: A 1.0 Service Appendix

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK A 1.0 Service appendix ATTENTION ! The settings described in this section relating to the service menu are intended for use by skilled persons because the functions and limits of the feed system can be greatly influenced by their…

  • Page 30
    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK Frequency adjustment range The control unit is supplied with a maximum frequency range of 5…150Hz. Using an adjustable under and over frequency limits, the user range (parameter F) can be restricted to a maximum ratio of 1:4.
  • Page 31
    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK Enable Service Mode The actual service menu is accessed by opening the service mode. 0 = Service mode off I = Service mode on Running mode The normal service menu, containing the output current and frequency limit settings, is accessed by opening the service mode.
  • Page 32: A 2.0 Accessories / Spare Parts

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK A 2.0 Accessories / Spare Parts Reo Order Type: Accessories / Spare Parts: Number: Manufacturer Order Number: Harting: 09 20 003 2711 + 19 20 003 1440 + mains input coupling 19 00 000 5082 + 09 20 000 9918…

  • Page 33
    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK…
  • Page 34
    Headquarters — Germany REO ELEKTRONIK AG Brühler Straße 100 · D-42657 Solingen Tel.: +49 (0)212 8804 0 · Fax: +49 (0)212 8804 188 REO INDUCTIVE COMPONENTS AG Brühler Straße 100 · D-42657 Solingen Tel.: +49 (0)212 8804 0 · Fax: +49 (0)212 8804 188 E-Mail: info@reo.de…

REOVIB MFS 268 UL/CSA

Operating Instructions

ELEKTRONIK

Errors are indicated by an alternating code and ERROR display

Overload limit

Output level exceeded e.g. incorrect frequency setting, coil air-

gap to wide.

Short circuit trip

Faulty coil, short circuit or defective cable..

Over voltage

Supply voltage too high or back EMF from the coil at lower fre-

quencies.

Current spike limit

Frequency set too low for installed coil or frequency altered too

rapidly during setting up.

Sensor fault (only when regulation mode is selected)

Accelerometer not working or faulty.

ERROR Reset through Menu C009

Sensor time out

After sensor time out has elapsed

ERROR Reset is achieved by pressing touch panel keys 0 or I during normal operation or by using

Menu C009.

In the event of an error check that this is not caused by incorrect wiring or cable faults. The error mes-

sage, ERROR ACC, can also occur if regulation mode is chosen (in Menu C008) and an accelerometer is

not connected, for example.

Reset the error in the following manner:

ERROR RESET

Clear Error

P

P

Frequently appearing Errors, which are not described in this chapter, should be reported to the

manufacturer.

19

  • Page 1
    REOVIB Control Equipment for the Vibratory Feeder Industry MFS 268 Frequency Converter for Vibratory Feeders UL / CSA — Version 268_UL-CSA_ANL_EN_47-13.DOC 21.11.2013…
  • Page 2: Technical Safety Instructions For The User

    The units described herein are electrical controllers for installation in industrial plant. They are designed for controlling vibratory feeders. For use in NFPA 79 Applications only Adapters providing field wiring means are available from REO ELEKTRONIK AG. Refer to REO ELEKTRONIK AG.

  • Page 3: Table Of Contents

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK Contents Technical safety instructions for the user ………………… 1 1.0 General …………………………3 2.0 Function …………………………3 2.1 Track control ……………………….4 2.2 Operating with two speeds (2 set points for coarse/fine switching) ………… 4 2.3 Control inputs and output ……………………

  • Page 4: General

    ELEKTRONIK 1.0 General The REOVIB MFS 268 range comprises special, adaptable controllers for use with vibratory feeders. The units generate an output frequency, to drive feeders, that is independent of mains frequency and so exact tuning with springs is not necessary. The feeders also run quieter because of the sinusoidal output signal.

  • Page 5: Track Control

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 2.1 Track control output switched ON and OFF Sensor from a track component sensor, using internal, adjustable time delays (ton Feeder and toff). The queue of components rises above and drops below the track sensor…

  • Page 6: Output Status Relay

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 2.3.4 Output status relay Status-Relay contact 250 V/1 A (changeover). Relay closes when the feeder is running – the relay opens when there is no enable signal or a fault displayed. 2.3.5 Time-Out output 24 VDC «time Out»…

  • Page 7: Technical Data

    For use in NFPA 79 Applications only E217179 Adapters providing field wiring means are available from REO ELEKTRONIK AG. Refer to REO ELEKTRONIK AG. 6.0 Declaration of Conformity We declare that these products conform with the following standards: EN 61000-6-4 and EN 61000-6-2 in accordance with the regulations of guidelines 2004/108/EC.

  • Page 8: Settings

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 7.0 Settings After checking the correct operation of the controller in conjunction with the vibratory feed system it is advisable to restrict the user to feeder throughput settings only. Setting the feeder throughput: Press the P key twice and adjust the throughput with the cursor keys (Code C.

  • Page 9: Control Elements

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 8.0 Control elements 8.1 Settings The six buttons and a LED display found in the front panel, are used for operating and setting up the unit. All operating methods and adjustable Display parameters can be set up through this panel.

  • Page 10: Commissioning

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 9.0 Commissioning 9.1 Assembling position Please fasten the devices on a vibration-free underground and take care for sufficient air circulation. 9.2 Preliminary steps • Check that the unit is correct for the local mains supply (rating plate information) and that it is correct- ly rated for the feed system.

  • Page 11: Putting The Equipment Into Operation

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 9.3 Putting the equipment into operation 1. Establish the vibrating frequency. 2. Establish the power of the feed system (maximum permissible current draw). For a new feeder where settings are unknown: (see also comments below) Without connecting the feeder, select parameter FAC in menu C210 (reset factory settings), press the cursor key to reset (SAFE) and press the P key to leave the menu.

  • Page 12: Setting Instructions

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 10.0 Setting Instructions 10.1 User adjustment of throughput Code C. 000 Feeder amplitude set point 0…100 % Running mode A further set point code can be found under C002 (for use in coarse/fine operation) Feeder amplitude set point 0…100 %…

  • Page 13: Track Control

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 10.2.2 Track control Code C. 167, 007 On time delay 0…60 sec. Off time delay 0…60 sec. 0 = No sensor inverting I = Sensor inverting 0 = Sensor time out not active I = Sensor time out active E.

  • Page 14: Pulse Feed

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 10.2.5 Pulse feed Code C. 004, 064 HOP. = 0 = continuous duty HOP. = I = pulse feed On time delay [sec.] Off time delay [sec.] Invert hopper sensor (not active) Running mode 10.2.6 Regulation mode…

  • Page 15: Instructions For Using Regulation Mode

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 10.2.6.1 Instructions for using regulation mode • An accelerometer e.g. SW 70 must be fitted to the vibratory feeder in order to run in regulation mode. The accelerometer should have a frequency range corresponding to that of the feeder.

  • Page 16
    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK In regulation mode the magnitude of the output signal has a direct affect on the maximum ampli- tude of the feeder. On bowl feeders it is advisable to fit the sensor as near as possible to the outside diameter and in this…
  • Page 17: Relationship Between Acceleration And Amplitude

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 10.2.6.3 Relationship between acceleration and amplitude The sensor measures the momentary acceleration of the feeder. It generates a sinusoidal output voltage signal. The acceleration gets higher as the frequency increases. The sensor signal is greater for a higher frequency and lower amplitude than for a low frequency with a higher amplitude.

  • Page 18: Optimisating Controller In Regulation Mode

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 10.2.6.6 Optimisating controller in regulation mode Setting the control range 1. In Menu C. 096 set parameter P (Max Limit) to 50 % 2. Set A (Feeder throughput) to 100% 3. Increase limit P from 50% until the required maximum feeder throughput is achieved The full set point adjustment range of 0…100% can now be used…

  • Page 19: Display Actual Current And Frequency

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 10.2.7 Display actual current and frequency Code C. 040 Actual current (display only) Actual frequency (display only) Running mode 10.2.8 Save selected parameters Code C. 143 Choose user parameter set Save new parameters Running mode 10.2.9 Recall user or factory settings…

  • Page 20: Error Messages / Error Reset

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 11.0 Error messages / ERROR reset Errors are indicated by an alternating code and ERROR display Overload limit Output level exceeded e.g. incorrect frequency setting, coil air- gap to wide. Short circuit trip Faulty coil, short circuit or defective cable..

  • Page 21: Connections For Enclosed Construction (Ip 54): 6-8 A Units

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 12.0 Connections for enclosed construction (IP 54): 6-8 A Units Internal connections When a potentiometer is connected parameter POT must be set to I in Menu C003. Status- relay 1 2 3 4…

  • Page 22: Connections For Enclosed Construction (Ip 54): 12 A Units

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 12.1 Connections for enclosed construction (IP 54): 12 A Units Internal connections Status relay Time out +24 V Air valve +24 V +24 V Accelerometer SW… INPUT Set point (external) +10V 0(4)…20mA 0…10V…

  • Page 23: Connections For Enclosed Construction (Ip 54): 16 A Units

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 12.2 Connections for enclosed construction (IP 54): 16 A Units Internal connections Status relay Time out +24 V Air valve +24 V +24 V Accelerometer SW… INPUT Set point (external) +10V 0(4)…20mA 0…10V…

  • Page 24: Connections For Panel Mounting Construction (Ip 20): 3 A, 6 A, 8 A

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 13.0 Connections for panel mounting construction (IP 20): 3 A, 6 A, 8 A REOVIB MFS268 Material-Sensor +24V Enable 12…24V, DC Set point 0…10V 0(4)…20mA R=500 OHM black External INPUT orange SW… + 24V…

  • Page 25: Connections For Panel Mounting Construction (Ip 20): 16A

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 13.1 Connections for panel mounting construction (IP 20): 16A line choke Mains L, N, PE / 115V/230V, 50/60HZ Material sensor +24V Enable 12…24V, DC Set point 0(4)…20mA 0…10V SPEED +10V black orange INPUT Accelerometer SW…

  • Page 26: Dimensions For 3 A, 6 A, 8 A Units

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 14.0 Dimensions for 3 A, 6 A, 8 A Units Enclosed construction, (IP 54) Ø5,0 REOVIB MFS 268 SPEED www.reo.de Ø5,0 Panel mounting construction, (IP 20) Ø 5,0 Ø 5,0 REOVIB MFS268 REOVIB MFS268 Ø…

  • Page 27: Dimensions Of Enclosed Construction (Ip 54) 12 A

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 14.1 Dimensions of enclosed construction (IP 54) 12 A Ø5,0 REOVIB MFS 268 SPEED www.reo.de Ø5,0 14.2 Dimensions of enclosed construction (IP 54) 16 A Ø5,0 REOVIB MFS 268 SPEED www.reo.de Ø5,0…

  • Page 28: Dimensions Of Panel Mounting Construction (Ip 20) 16 A

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 14.3 Dimensions of Panel mounting construction (IP 20) 16 A Ø5,0 SPEED +10V Ø5,0…

  • Page 29: A 1.0 Service Appendix

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK A 1.0 Service appendix ATTENTION ! The settings described in this section relating to the service menu are intended for use by skilled persons because the functions and limits of the feed system can be greatly influenced by their…

  • Page 30
    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK Frequency adjustment range The control unit is supplied with a maximum frequency range of 5…150Hz. Using an adjustable under and over frequency limits, the user range (parameter F) can be restricted to a maximum ratio of 1:4.
  • Page 31
    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK Enable Service Mode The actual service menu is accessed by opening the service mode. 0 = Service mode off I = Service mode on Running mode The normal service menu, containing the output current and frequency limit settings, is accessed by opening the service mode.
  • Page 32: A 2.0 Accessories / Spare Parts

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK A 2.0 Accessories / Spare Parts Reo Order Type: Accessories / Spare Parts: Number: Manufacturer Order Number: Harting: 09 20 003 2711 + 19 20 003 1440 + mains input coupling 19 00 000 5082 + 09 20 000 9918…

  • Page 33
    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK…
  • Page 34
    Headquarters — Germany REO ELEKTRONIK AG Brühler Straße 100 · D-42657 Solingen Tel.: +49 (0)212 8804 0 · Fax: +49 (0)212 8804 188 REO INDUCTIVE COMPONENTS AG Brühler Straße 100 · D-42657 Solingen Tel.: +49 (0)212 8804 0 · Fax: +49 (0)212 8804 188 E-Mail: info@reo.de…

(Ocr-Read Summary of Contents of some pages of the REO REOVIB MFS 268 Document (Main Content), UPD: 05 April 2023)

  • 8, REOVIB MFS 268 Operating Instructions EtherNet/IP — Programming 8 5.2.3 Receive, Acknowledge Write Enable H-Byte L-Byte Wor d 1 xxxx H (undefined) 0 0 0 E H-Byte L-Byte Wo rd 2 C0DE H C0 DE H-Byte L-Byte W ord 3 B5E7 H B5 E7 H-Byte L-Byte Word 4 C0DE H C0 DE The parameters can be sent after receipt of the acknowledge 5.2.4 Send Paramete…

  • 2, REO REOVIB MFS 268 REOVIB MFS 268 Operating Instructions EtherNet/IP — Programming 2 Technical safety instructions for the user This description contains the necessary information for the correct application of the product described below. It is intended for use by technically qualified personal. Qualified personnel are persons who, because of their training, experience and position as well as their knowledge of appropriate standards, regulations, health an…

  • 11, REO REOVIB MFS 268 REOVIB MFS 268 Operating Instructions EtherNet/IP — Programming 11 Parameter: Adjustment Display- Code Factory Setting: Entry code Parameter address HEX (.bit) Value HEX Service limits • Enable service menu 0 / I En.S. 0 127 0x5834 0x0000 / 0x FFFF • Show output current (0… 100 %) i. 040 0x200A 0x0000…0x8000 H • Show active vibration frequency F. 040 0x1005 0x01F4…0x7530 H •…

  • 3, REOVIB MFS 268 Operating Instructions EtherNet/IP — Programming 3 Contents Technical safety instructions for the user ……………………………………………………………………………………….. 2 1.0 General ………………………………………………………………………………………………………………………………… 4 2.0 Interface operation (EtherNet-IP ) …….…

  • 16, REOVIB MFS 268 Operating Instructions EtherNet/IP — Programming 16 5. Then you double-click on „Internet Protocol Version 4 (TCP/IPv4)“ 6. Then you set the subnet mask at 255.255.240.0. 7. You click on „OK“. 8. Then you open the web browser (e.g. the Internet-Explorer). 9. You enter the following IP-address 192.168.11.182 as address. 10. Then you click o…

  • 17, REOVIB MFS 268 Operating Instructions EtherNet/IP — Programming 17 8.2 DHCP Server Utility (Example: „BOOTP/DHCP Server“) 1. Please download a DHCP Server software for example: „DHCP/BOOTP Utility“. Important: Before you start the DHCP-server, note the MAC-address which has the following form: 00-00-BC-14-55-35. The MAC-address stands on the front of the module. 2. Start the DHCP-software.…

  • 13, REOVIB MFS 268 Operating Instructions EtherNet/IP — Programming 13 Example of switch parameter change Enable invert Open Write enable Word Code send Code Received 1 0000 H 0000 H 2 C0DE H Write Enable Address C0DE H Acknowledge 3 B5E7 H Write Enable Value B5E7 H Acknowledge 4 8000 H + Control bits Set mode bit = 1 C0DE H Acknowledge Write Parameter 1 0000 H 0000 H …

  • 10, REOVIB MFS 268 Operating Instructions EtherNet/IP — Programming 10 6.0 Parameter Table Non listed addresses cannot be altered! Parameter: Adjustment Display- Code Factory Setting: Entry code Parameter address HEX (.bit) Value HEX Vibratory feeder • Amplitude (throughput) 0…100 % A. 0 % 000, 002, 008, 096 100C 0x0000…0xFFFF • Second set point / coarse — fine 0…100 % 2. 0 002 0x1006 0x…

  • 5, REOVIB MFS 268 Operating Instructions EtherNet/IP — Programming 5 2.0 Interface operation (EtherNet-IP ) Bus Power Supply 24 V, DC, 250 mA Bus connector 2 x RJ-45 Internal interface CAN-Bus Supported baud rates 1000 kBaud Communication Data consistency required Protocol EtherNet-IP 3.0 Activate interface For the interface version parameter “CAN” is set to “I”.…

  • 4, REOVIB MFS 268 Operating Instructions EtherNet/IP — Programming 4 1.0 General The MFS 268 range of frequency converters for vibratory feeders can operate with an EtherNet-IP inter- face. In normal operation the set point, for the feeder throughput, can be sent from a PLC to the controller and the unit ready/fault status signals are fed back. In an additional parameter mode the unit can be config- ured over the EtherNet-IP. An external power supply of 24 VDC…

  • 9, REOVIB MFS 268 Operating Instructions EtherNet/IP — Programming 9 5.2.5 Close write enable H-Byte L-Byte Wort d 0000 H 0 0 0 0 H-Byte L-Byte Word 2 Write Enable Address = C0DE H C0 DE H-Byte L-Byte Word 3 Enable Value 0000 00 00 H-Byte L-Byte Word 4 Control — Word + 8000 H Mode bit must be set to `1`! All …

  • 15, REOVIB MFS 268 Operating Instructions EtherNet/IP — Programming 15 8.0 Methods for adjusting the IP-address 1. Web server (Preferably) 2. DHCP Server Utility If you don’t have a browser, you can push a switch on the front of our device. If you push this switch shorter than five seconds, the device gets the IP-address 192.168.11.182. If you push this switch longer than five seconds, the device is set into the original state (IP-address 0.0.0.0) and DHCP …

  • 1, MFS_268_EtherNetIP_appendix_rev03.en 02.08.2016 REOVIB Control Equipment for the Vibratory Feeder Industry MFS 268 Frequency Converter for Vibratory Feeders Appendix: EtherNet-IP — Programming

  • 7, REO REOVIB MFS 268 REOVIB MFS 268 Operating Instructions EtherNet/IP — Programming 7 5.2 Parameter Operation In parameter operation, the specific unit parameters can be monitored and adjusted. A `write` enable must be transmitted before parameters can be altered. On closing, the `write` enable must be cancelled. A `read` request must be sent before data can be read. Word 3 in the acknowledge i…

  • 6, REOVIB MFS 268 Operating Instructions EtherNet/IP — Programming 6 5.1 Programming for the Bus operation In normal operation the set point for Amplitude (throughout/feed rate) and the digital control signals, such as enable are set across the interface. The actual voltage/current values and unit status (ready or fault) are fed back. All data words are within the range 0…FFFF H. The following communication words are given in bit form. 5.1.1 Send to Controller H-B…

  • 20, REO REOVIB MFS 268 REO AG Brühler Straße 100 · D-42657 Solingen Tel.: +49 (0)212 8804 0 · Fax: +49 (0)212 8804 188 E-Mail: [email protected] Internet: www.reo.de PRODUCTION+SALES: China REO Shanghai Inductive Components Co., Ltd No. 536 ShangFeng Road · Pudong, 201201 Shanghai · China Tel.: +86 (0)21 5858 0686 · Fax: +86 (0)21 5858 0289 E-Mail: [email protected]…

  • 12, REOVIB MFS 268 Operating Instructions EtherNet/IP — Programming 12 7.0 Example of bus communication with Frequency controller Variable values are shown in italics. 7.1 Normal mode (Set point to 70 %) Send Set point Word Code send Code Received 1 0000 H 0000 H 2 B332 H Set point = 70 % — — 3 4 0004 H Enable On A5xx H Ready Enable ON, Stop controller (with enable) Send Set point Wo…

[Page 1] Reo Elektronik REOVIB MFS 268

268_UL-CSA_ANL_EN_47-13.DOC 21.11.2013 REOVIB Control Equipment for the Vibratory Feeder Industry MFS 268 Frequency Converter for Vibratory Feeders UL / CSA — Version …

[Page 2] Reo Elektronik REOVIB MFS 268

REOVIB MFS 268 UL/CSA Operating Instructions 1 ELEKTRONIK Technical safety instructions for the user This description contains the necessary information for the correct application of the product described below. It is intended for u…

[Page 3] Reo Elektronik REOVIB MFS 268

REOVIB MFS 268 UL/CSA Operating Instructions 2 ELEKTRONIK Contents Technical safety instructions for the user ……………………………………………………………………………………….. 1 1.0 General ……………….

[Page 4] Reo Elektronik REOVIB MFS 268

REOVIB MFS 268 UL/CSA Operating Instructions 3 ELEKTRONIK 1.0 General The REOVIB MFS 268 range comprises special, adaptable controllers for use with vibratory feeders. The units generate an output frequency, to drive feeders, that is ind…

[Page 5] Reo Elektronik REOVIB MFS 268

REOVIB MFS 268 UL/CSA Operating Instructions 4 ELEKTRONIK t ON t OFF Sensor Feeder ON OFF ON OFF Soft Start Soft Stop 2.1 Track control The output can be switched ON and OFF from a track c…

[Page 6] Reo Elektronik REOVIB MFS 268

REOVIB MFS 268 UL/CSA Operating Instructions 5 ELEKTRONIK 2.3.4 Output status relay Status-Relay contact 250 V/1 A (changeover). Relay closes when the feeder is running – the relay opens when there is no enable signal or a fault displa…

[Page 7] Reo Elektronik REOVIB MFS 268

REOVIB MFS 268 UL/CSA Operating Instructions 6 ELEKTRONIK 4.0 Technical Data Model Type MFS 268 / 3A MFS 268 / 6A MFS 268 / 8A MFS 268 / 12A MFS 268 / 16A Supply voltage 110 V, 240 V +/- 10 %, 50/60 Output 0…95 V, 0…205 V…

[Page 8] Reo Elektronik REOVIB MFS 268

REOVIB MFS 268 UL/CSA Operating Instructions 7 ELEKTRONIK 7.0 Settings After checking the correct operation of the controller in conjunction with the vibratory feed system it is advisable to restrict the user to feeder throughput sett…

[Page 9] Reo Elektronik REOVIB MFS 268

REOVIB MFS 268 UL/CSA Operating Instructions 8 ELEKTRONIK I 0 P F ON OFF Display ACCEPT or SKIP FUNCTION Reduce Increase Back 8.0 Control elements 8.1 Settings The six buttons and a LED display found in the front panel, are used …

[Page 10] Reo Elektronik REOVIB MFS 268

REOVIB MFS 268 UL/CSA Operating Instructions 9 ELEKTRONIK 9.0 Commissioning 9.1 Assembling position Please fasten the devices on a vibration-free underground and take care for sufficient air circulation. 9.2 Preliminary ste…

[Page 11] Reo Elektronik REOVIB MFS 268

REOVIB MFS 268 UL/CSA Operating Instructions 10 ELEKTRONIK 9.3 Putting the equipment into operation 1. Establish the vibrating frequency. 2. Establish the power of the feed system (maximum permissible current draw). For a new feeder wh…

[Page 12] Reo Elektronik REOVIB MFS 268

REOVIB MFS 268 UL/CSA Operating Instructions 11 ELEKTRONIK 10.0 Setting Instructions 10.1 User adjustment of throughput Code C. 000 A further set point code can be found under C002 (for use in coarse/fine operation) …

[Page 13] Reo Elektronik REOVIB MFS 268

REOVIB MFS 268 UL/CSA Operating Instructions 12 ELEKTRONIK 10.2.2 Track control 10.2.3 Sensor time out 10.2.4 Set point source Code C. 003 P P P P P P P P P F P 0 = Set point using display I = External set point 0 = External se…

[Page 14] Reo Elektronik REOVIB MFS 268

REOVIB MFS 268 UL/CSA Operating Instructions 13 ELEKTRONIK 10.2.5 Pulse feed Code C. 004, 064 10.2.6 Regulation mode Code C. 008 Vibrating Frequency [Hz] Max. output 100…5 % P P P P P P P P P P …

[Page 15] Reo Elektronik REOVIB MFS 268

REOVIB MFS 268 UL/CSA Operating Instructions 14 ELEKTRONIK 10.2.6.1 Instructions for using regulation mode • An accelerometer e.g. SW 70 must be fitted to the vibratory feeder in order to run in regulation mode. The accelerometer should…

[Page 16] Reo Elektronik REOVIB MFS 268

REOVIB MFS 268 UL/CSA Operating Instructions 15 ELEKTRONIK In regulation mode the magnitude of the output signal has a direct affect on the maximum ampli- tude of the feeder. On bowl feeders it is advisable to fit the sensor as near as …

[Page 17] Reo Elektronik REOVIB MFS 268

REOVIB MFS 268 UL/CSA Operating Instructions 16 ELEKTRONIK 10.2.6.3 Relationship between acceleration and amplitude The sensor measures the momentary acceleration of the feeder. It generates a sinusoidal output voltage signal. The accelerati…

[Page 18] Reo Elektronik REOVIB MFS 268

REOVIB MFS 268 UL/CSA Operating Instructions 17 ELEKTRONIK 10.2.6.6 Optimisating controller in regulation mode Setting the control range 1. In Menu C. 096 set parameter P (Max Limit) to 50 % 2. Set A (Feeder throughput) to 100% 3…

[Page 19] Reo Elektronik REOVIB MFS 268

REOVIB MFS 268 UL/CSA Operating Instructions 18 ELEKTRONIK 10.2.7 Display actual current and frequency Code C. 040 10.2.8 Save selected parameters Code C. 143 10.2.9 Recall user or factory settings Code C. 210 10.2.1…

[Page 20] Reo Elektronik REOVIB MFS 268

REOVIB MFS 268 UL/CSA Operating Instructions 19 ELEKTRONIK 11.0 Error messages / ERROR reset Errors are indicated by an alternating code and ERROR display Overload limit Output level exceeded e.g. incorrect frequency setting, coil …

[Page 21] Reo Elektronik REOVIB MFS 268

REOVIB MFS 268 UL/CSA Operating Instructions 20 ELEKTRONIK 12.0 Connections for enclosed construction (IP 54): 6-8 A Units Internal connections When a potentiometer is connected parameter POT must be set to I in Menu C003. …

[Page 22] Reo Elektronik REOVIB MFS 268

REOVIB MFS 268 UL/CSA Operating Instructions 21 ELEKTRONIK 12.1 Connections for enclosed construction (IP 54): 12 A Units Internal connections Track control sensor Enable Set poi…

[Page 23] Reo Elektronik REOVIB MFS 268

REOVIB MFS 268 UL/CSA Operating Instructions 22 ELEKTRONIK 12.2 Connections for enclosed construction (IP 54): 16 A Units Internal connections Track control sensor Enable Set point (…

[Page 24] Reo Elektronik REOVIB MFS 268

REOVIB MFS 268 UL/CSA Operating Instructions 23 ELEKTRONIK 13.0 Connections for panel mounting construction (IP 20): 3 A, 6 A, 8 A The …

[Page 25] Reo Elektronik REOVIB MFS 268

REOVIB MFS 268 UL/CSA Operating Instructions 24 ELEKTRONIK 13.1 Connections for panel mounting construction (IP 20): 16A Spring-clamp for sc…

[Page 26] Reo Elektronik REOVIB MFS 268

REOVIB MFS 268 UL/CSA Operating Instructions 25 ELEKTRONIK 14.0 Dimensions for 3 A, 6 A, 8 A Units Enclosed construction, (IP 54) Panel mounting construction, (IP 20) 3A 6A 8A A — 90 100 B — 45 50 C — 191 209 D …

[Page 27] Reo Elektronik REOVIB MFS 268

REOVIB MFS 268 UL/CSA Operating Instructions 26 ELEKTRONIK 14.1 Dimensions of enclosed construction (IP 54) 12 A 14.2 Dimensions of enclosed construction (IP 54) 16 A …

[Page 28] Reo Elektronik REOVIB MFS 268

REOVIB MFS 268 UL/CSA Operating Instructions 27 ELEKTRONIK 14.3 Dimensions of Panel mounting construction (IP 20) 16 A …

[Page 29] Reo Elektronik REOVIB MFS 268

REOVIB MFS 268 UL/CSA Operating Instructions 28 ELEKTRONIK A 1.0 Service appendix ATTENTION ! The settings described in this section relating to the service menu are intended for use by skilled persons because the functions and limits o…

[Page 30] Reo Elektronik REOVIB MFS 268

REOVIB MFS 268 UL/CSA Operating Instructions 29 ELEKTRONIK Frequency adjustment range The control unit is supplied with a maximum frequency range of 5…150Hz. Using an adjustable under and over frequency limits, the user range (parame…

[Page 31] Reo Elektronik REOVIB MFS 268

REOVIB MFS 268 UL/CSA Operating Instructions 30 ELEKTRONIK Enable Service Mode The actual service menu is accessed by opening the service mode. The normal service menu, containing the output current and frequency limit…

[Page 32] Reo Elektronik REOVIB MFS 268

REOVIB MFS 268 UL/CSA Operating Instructions 31 ELEKTRONIK A 2.0 Accessories / Spare Parts Type: Accessories / Spare Parts: Reo Order Number: Manufacturer Order Number: MFS 6A-8A mains input coupling ( HAN 3A-BU-S ) 9…

[Page 33] Reo Elektronik REOVIB MFS 268

REOVIB MFS 268 UL/CSA Operating Instructions 32 ELEKTRONIK

[Page 34] Reo Elektronik REOVIB MFS 268