Mpx контроллер ошибки

ENG

In addition, the HACCP alarm menu allows the following operations:

• delete an HACCP alarm by pressing Set & DOWN for 5 seconds when

displaying the list of alarms. This causes the HACCP to fl ash, the display

shows the message rES and the monitoring of HACCP alarms is

reinitialised;

• delete the entire memory of HACCP alarms, by pressing Set & UP &

DOWN for 5 seconds. This procedure displays the message rES, deletes

the entire memory of alarms and reinitialises the monitoring of the

HACCP alarms.

Display

Cause of the alarm

code

rE

Control probe fault

E1

Probe S1 fault

E2

Probe S2 fault

E3

Probe S3 fault

E4

Probe S4 fault

E5

Probe S5 fault

E6

Probe S6 fault

E7

Probe S7 fault

E8

Serial probe S8 not updated

E9

Serial probe S9 not updated

E10

Serial probe S10 not updated

E11

Serial probe S11 not updated

LO

Low temperature alarm

HI

High temperature alarm

LO2

Low temperature alarm

HI2

High temperature alarm

Immediate alarm from

IA

external contact

Delayed alarm from external

dA

contact

dor

Door open for too long alarm

Etc

Real time clock fault

LSH

Low superheat alarm

Low suction temperature

LSA

alarm

Maximum evaporation

MOP

pressure alarm

Low evaporation temperature

LOP

alarm

bLo

Valve blocked alarm

Communication error with

Edc

stepper driver

Stepper motor broken/not

EFS

connected

EE

Flash unit parameter error

EEPROM operating parameter

EF

error

HA

Type HA HACCP alarm

HF

Type HF HACCP alarm

Communication error with

MA

Master (only on Slave)

Communication error with

u1…u5

Slave (only on Master)

Alarm on unit 1 to 5 in the

n1…n5

network

Upload procedure with errors

up1…up5

on unit 1 to 5

Displayed probe wrong or

205

disconnected

MPXPRO — + 0300055EN rel. 1.0 30/08/10

Icon

Alarm

fl ash on

Buzzer

Reset

relay

display

ON

ON

automatic

OFF

OFF

automatic

OFF

OFF

automatic

OFF

OFF

automatic

OFF

OFF

automatic

OFF

OFF

automatic

OFF

OFF

automatic

OFF

OFF

automatic

OFF

OFF

automatic

OFF

OFF

automatic

OFF

OFF

automatic

OFF

OFF

automatic

ON

ON

automatic

ON

ON

automatic

ON

ON

automatic

ON

ON

automatic

ON

ON

automatic

ON

ON

automatic

ON

ON

automatic

OFF

OFF

automatic

OFF

OFF

automatic

automatic /

OFF

OFF

manual

OFF

OFF

automatic

OFF

OFF

automatic

manual/

OFF

OFF

disabled with

P14=0

ON

ON

automatic

ON

ON

automatic

OFF

OFF

automatic

OFF

OFF

automatic

OFF

OFF

manual

OFF

OFF

manual

ON

ON

automatic

ON

ON

automatic

ON

ON

automatic

OFF

OFF

OFF

OFF

Evaporator

Compressor

Defrost

fans

duty

unchanged

unchanged

setting(c4)

duty

unchanged

unchanged

setting(c4)

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

duty

unchanged

unchanged

setting(c4)

duty

unchanged

unchanged

setting(c4)

duty

unchanged

unchanged

setting(c4)

duty

unchanged

unchanged

setting(c4)

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

duty

unchanged

unchanged

setting(A6)

duty

setting(A6)

unchanged

unchanged

if A7≠0

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

OFF

unchanged

unchanged

OFF

(paragraph

unchanged

unchanged

6.10)

OFF

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

OFF

not performed

OFF

OFF

not performed

OFF

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

64

Network

Continuous

Signalled on

solenoid

cycle

tLAN

valve

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

not performed

not performed

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

unchanged

Tab. 9.b

  • Contents

  • Table of Contents

  • Troubleshooting

  • Bookmarks

Quick Links

loading

Related Manuals for Carel IRMPX00000

Summary of Contents for Carel IRMPX00000

  • Page 1
    User manual…
  • Page 3
    We wish to save you time and money! We can assure you that a thorough reading of this manual will guarantee correct installation and safe use of the product described.
  • Page 5
    CONTENTS General Features ……………………………………………………………………………………………………………………………2 Main features of the multiplexed Master/Slave units……………………3 Models in the MPX series…………………………… 5 Installation ………………………………..6 Electrical connections …………………………..6 User interface — Buttons and display…………………………7 The LED display …………………………….7 Operating indications …………………………… 7 Keypad …………………………………
  • Page 7: General Features

    General Features The multiplexed Master/Slave units belong to the MPX Series for refrigeration, made up of microprocessor-controlled electronic controllers with LED display, specifically designed for the management of refrigeration units. In this particular case the refrigeration units may be stand-alone type or grouped together as multiplexed cabinets. 1.

  • Page 8
    Quality control includes a rigorous ‘TEST-IN-CIRCUIT’ on each single component to ensure that the controller is completely reliable. NTC probe The MPX instruments have been designed to be connected to Carel NTC probes, as these offer greater precision than other probe types. Watchdog A special device that protects the microprocessor of the controller even in the event of strong electromagnetic noise.
  • Page 9: Models In The Mpx Series

    The models in the MPX series have different codes according to their features. The table below lists the various codes and the corresponding options that characterise each model: OPTIONS MODEL CODE RS485 4 RELAY BUZZER IRMPX00000 • IRMPX0M000 • IRMPX0A000 • IRMPX10000 •…

  • Page 10: Installation

    3. Installation Actual installation: 1) insert the instrument into the previously-created opening; 2) fasten the instrument to the panel by sliding it onto the fastening bracket. 3) insert the rear connectors of the instrument into the corresponding pre-wired connectors 4) close the panel 5) connect the power and configure the operating parameters.

  • Page 11: User Interface — Buttons And Display

    4. User interface — Buttons and display Each instrument features: • 12Vac power supply; • two and a half digit display; • temperature display to the tenths; • LED indicating the output state; • 4 buttons for programming; • buzzer (according to model) PANEL-MOUNTED VERSION 4.1 The LED display The display shows temperature in the range -55 to 95ºC.

  • Page 12
    — stops the audible alarm for 10 minutes(only if fitted); if pressed for over 5 seconds: — accesses the menu of the type “F” parameters (frequent); if pressed for more than 5 seconds together with button 9: — accesses the menu of the type ‘C’ parameters (configuration); — accesses the alarm log via password ( = 44) — activates the parameter download from the Master units, via password (=66) if pressed at instrument start-up:…
  • Page 13: Configuration Of The Controllers

    5. Configuration of the controllers. The multiplexed units are supplied ready for use. They have in fact been programmed using a default configuration so as to satisfy the more common requirements. Programming is performed by assigning all the parameters the more-frequently required value. These values are listed in the table of parameters at the end of the manual.

  • Page 14: Other Important Parameters

    5.3 Other important parameters LAN configuration parameters: For the Master: • parameter “Sn” (Slave number): from 1 to 5; number of Slaves in the LAN; during boot the display shows “uM” : unit-Master • parameters for setting defrost times: “hx”, “mx”; x = 1, 2,… , 8: hours and minutes of defrost times; the tens of minutes can be set (only if RTC is present) •…

  • Page 15: List Of Parameters To Be Checked During Installation

    dt: End defrost temperature This parameter allows the end defrost temperature, as measured on the evaporator, to be set. In any case, the maximum defrost time is equal to the value, in minutes, set for parameter dP. When the temperature measured by the defrost end probe is higher than the defrost end temperature set by the user, the defrost cycle will not be performed, that is, only the following dripping and, if required, post-dripping phases will take place.

  • Page 16: Programming

    6. Programming The microprocessor in the MPX instruments allows the configuration of the functions of the controller according to the application requirements. To simplify this operation, we have divided the operating parameters into two main groups: • frequently used parameters (indicated as ‘F’ parameters in the tables below); •…

  • Page 17: Exiting The Programming Procedure

    How to exit the procedure How to save the new set values • Press to save the new values and exit the procedure. Important: press to save the new values. In the case of power failure before has been pressed, all changes will be lost. 6.3 Exiting the programming procedure To exit the programming procedure without saving the changes, do not press any key for at least 60 seconds (TIME OUT).

  • Page 18: Programming By Remote Control

    7. Programming by remote control (AVAILABLE FOR THE FOLLOWING MODELS: IRMPX0A000, IRMPX1A000, IRMPXMA000) 7.1 Remote control layout Remote-local interface buttons: PRG, SEL, KEY_UP, KEY_DOWN Numeric keypad Fig. 1 (I): Function buttons; History, PSW, ESC, ENABLE. 7.2 Introduction. The remote control for the IRMPX series has been designed to provide the user, in the palm of their hand, all the functions offered by the MPX family instruments and its local network structure: 1.

  • Page 19: Technical Specifications

    7.3 Technical specifications Power supply 2 alkaline batteries, 1.5V (type UM-4 AAA, IEC R03) Case plastic Dimensions 60x160x18mm Storage -25°C÷ +70°C Operating temperature 0°C÷ 50°C Type of transmission Infrared Weight 80 g (without batteries) 7.4 Description of the keypad The buttons can be divided into the following groups, based on their functions,: •…

  • Page 20: The Psw Button And The Command Buttons

    7.5 The PSW button and the command buttons. 7.5.1 The button: enter the system password from the remote control Pressing the PSW button for at least 5 seconds accesses the enter prompt for the system password (see using the local keypad and Table of parameters): •…

  • Page 21
    7.6.3 ENABLING THE CONTROLLER FOR RECEIVING COMMANDS FROM THE REMOTE CONTROL ENABLE • press the button to enable the use of the remote control; • the instrument will display a two digit code (the value of parameter H3); enter the code displayed using the numeric keypad on the remote control. The code must be entered correctly, without ignoring the zeroes (e.g.
  • Page 22: Re-Configuring A Control With The Default Parameters

    8. Re-configuring a control with the default parameters Under exceptional conditions − high electromagnetic noise levels, for example − there may be errors when storing data. Consequently, the unit may not work correctly. When the microprocessor identifies an error in the process of storing data, one of the following groups of letters will be displayed: EA, EB, -E- The last symbol will only appear at the start-up of the instrument.

  • Page 23: The Alarm Log

    9. The alarm log All the models in the MPX Series are fitted with an alarm log that records up to until 9 alarm signals. The models configured as Master and fitted with RTC also allow the display of the age of each alarm, that is, the time in hours elapsed between the moment in which the log is consulted and the time the alarm was recorded.

  • Page 24: New Local Network Functions

    10. New local network functions 10.1 Network defrost for multiplexed systems The Master controls the defrost in the entire multiplexed island (cabinet controlled by the Master + cabinets controlled by the Slaves). This waits for all units to exit the actual defrost stage before sending the end defrost command to the entire network. The Slaves which have exited the actual defrost stage, await the end defrost command from the Master before passing to the dripping stage.

  • Page 25: Description Of The Configuration Parameters

    11. DESCRIPTION OF THE CONFIGURATION PARAMETERS 11.1 Configuration parameters As already mentioned, (see chapter on how to modify the operating parameters), there are two types of parameter: • parameters used frequently (indicated by ‘F’ in the following tables) • configuration parameters (type C), which are protected by a password to prevent unwanted modification. 11.2 Parameter categories Besides being divided into TYPES, the parameters are grouped into logical categories labelled by letters indicating their function.

  • Page 26: Parameters For The Management Of The Temperature Probes

    Short descriptive note about probes with NTC- and PTC-type thermistors: Units in the MPX series are designed to work with Carel NTC temperature probes, or probes using thermistors with a negative characteristic (NTC stands for Negative Temperature Coefficient). This type of thermistor modifies an electrical parameter (its own resistance) in inverse proportion to any change in temperature;…

  • Page 27
    /2: Stability of measurement This parameter is used to control the stability with which the temperature is measured. Low values assigned to this parameter produce a prompt response by the probe to variations in temperature; however, the display becomes correspondingly sensitive to changes. High values slow down the response, causing less fluctuation and a more stable reading.
  • Page 28: R = Parameters For Temperature Regulation

    /9: defrost with probe 3 This parameter allows a defrost to be carried out using probes S2 and S3 together, if set to 1. In this case the temperature defrost ends when the temperature measured by both probes is greater than or equal to that set as the end defrost temperature (See parameter “dt”). Probe 3 can therefore be used as a defrost probe on a second evaporator.

  • Page 29
    rd: Regulation delta Sets the value of the differential, or hysteresis, used in regulating the temperature. A narrow differential, i.e. one with a low number, ensures a temperature that differs little from the set-point (or optimal operating temperature), but one that requires the frequent switching on and off of the main operating components (normally the compressor).
  • Page 30: C = Parameters For Compressor Management

    To inhibit monitoring and/or reset the values recorded, set “r5” to 0. After 199 hours the measuring of the max. and min. temperatures is halted, having reached the maximum monitoring time allowed by the instrument. Modify “r5” to perform monitoring again (first set to 0 using the arrows and the SEL button and then to the required value between 1 and 5, again using the arrows and SEL.

  • Page 31
    c0: Delay in switching on the compressor and fans (if controlled) after switching on the instrument From when power is supplied to the controller, the start-up of the compressor is delayed by a time (in minutes) equal to the value assigned a this parameter.
  • Page 32
    c4: Duty setting or safety relay If the “regulation error” alarm occurs (that is, probes S1 and/or S3 are short-circuited or disconnected) this parameter ensures the operation of the compressor until of the elimination of the fault. As the compressor is unable to function based on the temperature (because of the faulty probe), it is activated cyclically with an operating time («ON time») in minutes equivalent to the value assigned to c4 and a fixed OFF time of 15 minutes.
  • Page 33: D = Parameters For Defrost Management

    11.7 d = Parameters for defrost management DEFROST PARAMETERS Type Max. Def. To LAN • Defrost types 0 = electrical: ends by temperature and/or for timeout 1 = hot gas: ends by temperature and/or for timeout 2 = electrical: ends for timeout 3= hot gas: ends for timeout •…

  • Page 34
    dt: End defrost temperature set-point This parameter allows the setting of the temperature of the evaporator at which the defrost is ended (the temperature of the evaporator is measured by the defrost probe: probe 2). If at the start of a defrost (d0 = 0) the temperature measured by the defrost probe is greater than the set end defrost temperature, the unit goes directly to the dripping phase (See further on, network defrost).
  • Page 35
    The defrost cycle thus becomes the condensate discharge cycle, which needs to be started at short intervals (minutes) and for very brief periods (seconds). Contact your Carel agent for further information. — Parameter can be transferred via LAN from the Master to its connected Slaves.
  • Page 36: A = Parameters For Alarm Control

    11.8 A = parameters for alarm control ALARM PARAMETERS Type Max. Def. °C/°F • Fan and alarm differential °C/°F • High temperature alarm: indicates the maximum variation from +199 the set-point. AH = 0 excludes the high temperature alarm °C/°F •…

  • Page 37: Digital Inputs And Description Of The Interface Commands For The Supervisor

    AL: Minimum temperature alarm This parameter allows the low temperature alarm to be selected. The value of AL does not indicate the temperature at which the alarm will sound, but rather the maximum deviation from the set-point (i.e. the requested operating temperature) that is permitted. The low temperature alarm is given as follows: Low temperature alarm <…

  • Page 38
    When the alarm ceases the unit resumes normal temperature control operation. WARNING: If A8 = 1 the alarm can be activated by a specific command from the supervisory system (if the latter exploits the functions supplied by the MPXs) or, on Slave units where A8 = 1, by the opening of the digital input DIN2 on the Master. Important note: it should be remembered that to guarantee the safety of the unit in the case of serious alarms, the unit itself must always be fitted with all the electro-mechanical safety devices needed to ensure correct operation.
  • Page 39
    A4/A5/A8 = 5: Door Switch Setting A4/A5/A8= 5 controls the switch on the store-room door. When the switch is opened the compressor and the fans are switched off and the lights are switched on (if at least one of the two fan or AUX relays is configured as an auxiliary and is used as a light relay). When the door is closed (as well as the Multifunction contact), the unit resumes the previous operation, delaying any temperature alarm by a number of hours equivalent to the value of d8.
  • Page 40
    A9: Enable the propagation via the LAN of the Master’s second digital input This parameter is accessible only for instruments configured as Master. It allows “parallel connection” to the virtual digital input on the connected Slave units of the Master’s second (physical) digital input DIN2. In this way, the second digital input of the Master may be propagated or not to the Slaves.
  • Page 41: F = Parameters For Controlling The Evaporator Fans

    11.10 F = parameters for controlling the evaporator fans FAN PARAMETERS Type Max. Def. To LAN • Fan management: flag 0 = fan always ON (except in special cases: see parameters F2, F3, Fd) 1 = fans thermostat-controlled in accordance with the absolute set-point F1 °C/°F •…

  • Page 42: H = Other Settings

    11.11 H = other settings OTHER PRE-SETTINGS Type Max. Def. To LAN Serial address (only for the network Master) Relay 4 selection: flag 0 = auxiliary output 1 = alarm relay, normally open (closed in alarm) 2 = alarm relay, normally closed (open in alarm) 3 = auxiliary relay: Master serves the Slaves;…

  • Page 43
    • In = 0: unit configured as Slave — Available on all models — The default for this parameter depends on the model of the instrument; see the second row of the following table for the default values of the various models: IRMPX00000 IRMPX0M000 IRMPX0A000 IRMPX10000…
  • Page 44: Operating States Of The Units

    12. Operating states of the units As indicated above, the display LEDs can be in three states: • off, when the function indicated or the actuator is not operative; • on, when the function indicated or the actuator is operative; •…

  • Page 45
    13. Alarms 13.1 Defective or incorrect operation The units in the MPX range are able to signal most incorrect operations automatically. When a malfunction occurs, the microprocessor initiates the following actions: • the malfunction is signalled on the display by an appropriate alarm code. More specifically, the display shows the alarm code and the temperature read by the probe, alternating in sequence.
  • Page 46: Alarms

    HI FLASHING High temperature alarm. The probe has measured a temperature further above the set value than the value set for parameter AH. • Check parameters AH, Ad and A0. • The alarm will cease as soon as the temperature returns within the set limits (see parameter AH). EA, EB DISPLAYED DURING OPERATION OR WHEN SWITCHING-ON Data acquisition error.

  • Page 47: Troubleshooting

    14. Troubleshooting PROBLEM CAUSE CHECK compressor does not start : compressor delay in progress parameters c0, c1 and c2 • power on • compressor LED flashing temperature is outside set limits but no alarm alarm delay in progress check Ad signalled and the buzzer, if fitted, does not sound the AL or Ad alarm signalled (Multi-function…

  • Page 48: Technical Specifications

    15. Technical specifications 15.1 Technical characteristics: Probe type: NTC Carel Operating field: -55°c — +95°c ± 0.5°C Precision : Storage: -10°C/ 70°c Operating conditions: 0°C/+50°c Power supply: 12Vac Power consumption: 150mA Front panel index of protection: IP65 with panel mounted and gasket inserted…

  • Page 49: Temperature/Resistance Ratios For Ntc Thermistors

    Rmax is the maximum value. For the sake of simplicity, the values corresponding to only a limited number of temperatures are given. Intermediate values can be determined by interpolation. Temperature/Resistance ratios for the Carel NTC temperature probe Temperature Rmin Rstd Rmax -40 ºC…

  • Page 50: View Of The Instrument

    15.3 View of the instrument Dimensions of the MPX in mm: 25/06/01 Cod. +030220191 rel. 2.0 dated…

  • Page 51: Wiring Diagrams

    16. WIRING DIAGRAMS Master/Slave connection wiring diagram: Transformer Transformer Transformer (*) Insulating Transformer transformer Example of wiring for serial connection of the instruments: Main = mains power supply TRF = transformer INS TRF = insulating transformer = earth SER = multiple connection to the controller system 16.1 MPX contact rear view: Label of connections for the IRMPX10000 model (slave with 4 relays): Label of connections for the IRMPXM0000 model (Master with 485):…

  • Page 52: Summary Of Parameters

    17. Summary of parameters PARAMETER Type Min. Max. Def. To LAN 2 PASSWORD PARAMETERS LOG PASSWORD DOWNLOAD PASSWORD PROBE PARAMETERS Type Min. Max. Def. To LAN Temperature set-point °C/°F -10.0 • °C/°F Regulation probe calibration Measurement stability Probe reading rate •…

  • Page 53
    COMPRESSOR PARAMETERS Type Min. Max. Def. To LAN • Compressor start delay when the instrument is turned ON min. • Minimum time between two successive compressor starts min. • Minimum compressor off time min. • Minimum compressor on time min. •…
  • Page 54
    FAN PARAMETERS Type Min. Max. Def. To LAN • Fan management: flag 0 = fan always ON (except in special cases: see parameters F2, F3, 1 = fans thermostat-controlled in accordance with the absolute set- point F1 °C/°F • Fan start absolute set-point Active if F0 = 1 •…
  • Page 55
    Note: ___________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________…
  • Page 56
    Note: ___________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________…
  • Page 57
    Note: ___________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________…
  • Page 59
    Agency: CAREL srl Via dell’Industria, 11 — 35020 Brugine — Padova (Italy) Tel. (+39) 049.9716611 Fax (+39) 049.9716600 http://www.carel.com — e-mail: carel@carel.com…

  • Page 1
    User manual…
  • Page 3
    We wish to save you time and money! We can assure you that a thorough reading of this manual will guarantee correct installation and safe use of the product described.
  • Page 5
    CONTENTS General Features ……………………………………………………………………………………………………………………………2 Main features of the multiplexed Master/Slave units……………………3 Models in the MPX series…………………………… 5 Installation ………………………………..6 Electrical connections …………………………..6 User interface — Buttons and display…………………………7 The LED display …………………………….7 Operating indications …………………………… 7 Keypad …………………………………
  • Page 7: General Features

    General Features The multiplexed Master/Slave units belong to the MPX Series for refrigeration, made up of microprocessor-controlled electronic controllers with LED display, specifically designed for the management of refrigeration units. In this particular case the refrigeration units may be stand-alone type or grouped together as multiplexed cabinets. 1.

  • Page 8
    Quality control includes a rigorous ‘TEST-IN-CIRCUIT’ on each single component to ensure that the controller is completely reliable. NTC probe The MPX instruments have been designed to be connected to Carel NTC probes, as these offer greater precision than other probe types. Watchdog A special device that protects the microprocessor of the controller even in the event of strong electromagnetic noise.
  • Page 9: Models In The Mpx Series

    The models in the MPX series have different codes according to their features. The table below lists the various codes and the corresponding options that characterise each model: OPTIONS MODEL CODE RS485 4 RELAY BUZZER IRMPX00000 • IRMPX0M000 • IRMPX0A000 • IRMPX10000 •…

  • Page 10: Installation

    3. Installation Actual installation: 1) insert the instrument into the previously-created opening; 2) fasten the instrument to the panel by sliding it onto the fastening bracket. 3) insert the rear connectors of the instrument into the corresponding pre-wired connectors 4) close the panel 5) connect the power and configure the operating parameters.

  • Page 11: User Interface — Buttons And Display

    4. User interface — Buttons and display Each instrument features: • 12Vac power supply; • two and a half digit display; • temperature display to the tenths; • LED indicating the output state; • 4 buttons for programming; • buzzer (according to model) PANEL-MOUNTED VERSION 4.1 The LED display The display shows temperature in the range -55 to 95ºC.

  • Page 12
    — stops the audible alarm for 10 minutes(only if fitted); if pressed for over 5 seconds: — accesses the menu of the type “F” parameters (frequent); if pressed for more than 5 seconds together with button 9: — accesses the menu of the type ‘C’ parameters (configuration); — accesses the alarm log via password ( = 44) — activates the parameter download from the Master units, via password (=66) if pressed at instrument start-up:…
  • Page 13: Configuration Of The Controllers

    5. Configuration of the controllers. The multiplexed units are supplied ready for use. They have in fact been programmed using a default configuration so as to satisfy the more common requirements. Programming is performed by assigning all the parameters the more-frequently required value. These values are listed in the table of parameters at the end of the manual.

  • Page 14: Other Important Parameters

    5.3 Other important parameters LAN configuration parameters: For the Master: • parameter “Sn” (Slave number): from 1 to 5; number of Slaves in the LAN; during boot the display shows “uM” : unit-Master • parameters for setting defrost times: “hx”, “mx”; x = 1, 2,… , 8: hours and minutes of defrost times; the tens of minutes can be set (only if RTC is present) •…

  • Page 15: List Of Parameters To Be Checked During Installation

    dt: End defrost temperature This parameter allows the end defrost temperature, as measured on the evaporator, to be set. In any case, the maximum defrost time is equal to the value, in minutes, set for parameter dP. When the temperature measured by the defrost end probe is higher than the defrost end temperature set by the user, the defrost cycle will not be performed, that is, only the following dripping and, if required, post-dripping phases will take place.

  • Page 16: Programming

    6. Programming The microprocessor in the MPX instruments allows the configuration of the functions of the controller according to the application requirements. To simplify this operation, we have divided the operating parameters into two main groups: • frequently used parameters (indicated as ‘F’ parameters in the tables below); •…

  • Page 17: Exiting The Programming Procedure

    How to exit the procedure How to save the new set values • Press to save the new values and exit the procedure. Important: press to save the new values. In the case of power failure before has been pressed, all changes will be lost. 6.3 Exiting the programming procedure To exit the programming procedure without saving the changes, do not press any key for at least 60 seconds (TIME OUT).

  • Page 18: Programming By Remote Control

    7. Programming by remote control (AVAILABLE FOR THE FOLLOWING MODELS: IRMPX0A000, IRMPX1A000, IRMPXMA000) 7.1 Remote control layout Remote-local interface buttons: PRG, SEL, KEY_UP, KEY_DOWN Numeric keypad Fig. 1 (I): Function buttons; History, PSW, ESC, ENABLE. 7.2 Introduction. The remote control for the IRMPX series has been designed to provide the user, in the palm of their hand, all the functions offered by the MPX family instruments and its local network structure: 1.

  • Page 19: Technical Specifications

    7.3 Technical specifications Power supply 2 alkaline batteries, 1.5V (type UM-4 AAA, IEC R03) Case plastic Dimensions 60x160x18mm Storage -25°C÷ +70°C Operating temperature 0°C÷ 50°C Type of transmission Infrared Weight 80 g (without batteries) 7.4 Description of the keypad The buttons can be divided into the following groups, based on their functions,: •…

  • Page 20: The Psw Button And The Command Buttons

    7.5 The PSW button and the command buttons. 7.5.1 The button: enter the system password from the remote control Pressing the PSW button for at least 5 seconds accesses the enter prompt for the system password (see using the local keypad and Table of parameters): •…

  • Page 21
    7.6.3 ENABLING THE CONTROLLER FOR RECEIVING COMMANDS FROM THE REMOTE CONTROL ENABLE • press the button to enable the use of the remote control; • the instrument will display a two digit code (the value of parameter H3); enter the code displayed using the numeric keypad on the remote control. The code must be entered correctly, without ignoring the zeroes (e.g.
  • Page 22: Re-Configuring A Control With The Default Parameters

    8. Re-configuring a control with the default parameters Under exceptional conditions − high electromagnetic noise levels, for example − there may be errors when storing data. Consequently, the unit may not work correctly. When the microprocessor identifies an error in the process of storing data, one of the following groups of letters will be displayed: EA, EB, -E- The last symbol will only appear at the start-up of the instrument.

  • Page 23: The Alarm Log

    9. The alarm log All the models in the MPX Series are fitted with an alarm log that records up to until 9 alarm signals. The models configured as Master and fitted with RTC also allow the display of the age of each alarm, that is, the time in hours elapsed between the moment in which the log is consulted and the time the alarm was recorded.

  • Page 24: New Local Network Functions

    10. New local network functions 10.1 Network defrost for multiplexed systems The Master controls the defrost in the entire multiplexed island (cabinet controlled by the Master + cabinets controlled by the Slaves). This waits for all units to exit the actual defrost stage before sending the end defrost command to the entire network. The Slaves which have exited the actual defrost stage, await the end defrost command from the Master before passing to the dripping stage.

  • Page 25: Description Of The Configuration Parameters

    11. DESCRIPTION OF THE CONFIGURATION PARAMETERS 11.1 Configuration parameters As already mentioned, (see chapter on how to modify the operating parameters), there are two types of parameter: • parameters used frequently (indicated by ‘F’ in the following tables) • configuration parameters (type C), which are protected by a password to prevent unwanted modification. 11.2 Parameter categories Besides being divided into TYPES, the parameters are grouped into logical categories labelled by letters indicating their function.

  • Page 26: Parameters For The Management Of The Temperature Probes

    Short descriptive note about probes with NTC- and PTC-type thermistors: Units in the MPX series are designed to work with Carel NTC temperature probes, or probes using thermistors with a negative characteristic (NTC stands for Negative Temperature Coefficient). This type of thermistor modifies an electrical parameter (its own resistance) in inverse proportion to any change in temperature;…

  • Page 27
    /2: Stability of measurement This parameter is used to control the stability with which the temperature is measured. Low values assigned to this parameter produce a prompt response by the probe to variations in temperature; however, the display becomes correspondingly sensitive to changes. High values slow down the response, causing less fluctuation and a more stable reading.
  • Page 28: R = Parameters For Temperature Regulation

    /9: defrost with probe 3 This parameter allows a defrost to be carried out using probes S2 and S3 together, if set to 1. In this case the temperature defrost ends when the temperature measured by both probes is greater than or equal to that set as the end defrost temperature (See parameter “dt”). Probe 3 can therefore be used as a defrost probe on a second evaporator.

  • Page 29
    rd: Regulation delta Sets the value of the differential, or hysteresis, used in regulating the temperature. A narrow differential, i.e. one with a low number, ensures a temperature that differs little from the set-point (or optimal operating temperature), but one that requires the frequent switching on and off of the main operating components (normally the compressor).
  • Page 30: C = Parameters For Compressor Management

    To inhibit monitoring and/or reset the values recorded, set “r5” to 0. After 199 hours the measuring of the max. and min. temperatures is halted, having reached the maximum monitoring time allowed by the instrument. Modify “r5” to perform monitoring again (first set to 0 using the arrows and the SEL button and then to the required value between 1 and 5, again using the arrows and SEL.

  • Page 31
    c0: Delay in switching on the compressor and fans (if controlled) after switching on the instrument From when power is supplied to the controller, the start-up of the compressor is delayed by a time (in minutes) equal to the value assigned a this parameter.
  • Page 32
    c4: Duty setting or safety relay If the “regulation error” alarm occurs (that is, probes S1 and/or S3 are short-circuited or disconnected) this parameter ensures the operation of the compressor until of the elimination of the fault. As the compressor is unable to function based on the temperature (because of the faulty probe), it is activated cyclically with an operating time («ON time») in minutes equivalent to the value assigned to c4 and a fixed OFF time of 15 minutes.
  • Page 33: D = Parameters For Defrost Management

    11.7 d = Parameters for defrost management DEFROST PARAMETERS Type Max. Def. To LAN • Defrost types 0 = electrical: ends by temperature and/or for timeout 1 = hot gas: ends by temperature and/or for timeout 2 = electrical: ends for timeout 3= hot gas: ends for timeout •…

  • Page 34
    dt: End defrost temperature set-point This parameter allows the setting of the temperature of the evaporator at which the defrost is ended (the temperature of the evaporator is measured by the defrost probe: probe 2). If at the start of a defrost (d0 = 0) the temperature measured by the defrost probe is greater than the set end defrost temperature, the unit goes directly to the dripping phase (See further on, network defrost).
  • Page 35
    The defrost cycle thus becomes the condensate discharge cycle, which needs to be started at short intervals (minutes) and for very brief periods (seconds). Contact your Carel agent for further information. — Parameter can be transferred via LAN from the Master to its connected Slaves.
  • Page 36: A = Parameters For Alarm Control

    11.8 A = parameters for alarm control ALARM PARAMETERS Type Max. Def. °C/°F • Fan and alarm differential °C/°F • High temperature alarm: indicates the maximum variation from +199 the set-point. AH = 0 excludes the high temperature alarm °C/°F •…

  • Page 37: Digital Inputs And Description Of The Interface Commands For The Supervisor

    AL: Minimum temperature alarm This parameter allows the low temperature alarm to be selected. The value of AL does not indicate the temperature at which the alarm will sound, but rather the maximum deviation from the set-point (i.e. the requested operating temperature) that is permitted. The low temperature alarm is given as follows: Low temperature alarm <…

  • Page 38
    When the alarm ceases the unit resumes normal temperature control operation. WARNING: If A8 = 1 the alarm can be activated by a specific command from the supervisory system (if the latter exploits the functions supplied by the MPXs) or, on Slave units where A8 = 1, by the opening of the digital input DIN2 on the Master. Important note: it should be remembered that to guarantee the safety of the unit in the case of serious alarms, the unit itself must always be fitted with all the electro-mechanical safety devices needed to ensure correct operation.
  • Page 39
    A4/A5/A8 = 5: Door Switch Setting A4/A5/A8= 5 controls the switch on the store-room door. When the switch is opened the compressor and the fans are switched off and the lights are switched on (if at least one of the two fan or AUX relays is configured as an auxiliary and is used as a light relay). When the door is closed (as well as the Multifunction contact), the unit resumes the previous operation, delaying any temperature alarm by a number of hours equivalent to the value of d8.
  • Page 40
    A9: Enable the propagation via the LAN of the Master’s second digital input This parameter is accessible only for instruments configured as Master. It allows “parallel connection” to the virtual digital input on the connected Slave units of the Master’s second (physical) digital input DIN2. In this way, the second digital input of the Master may be propagated or not to the Slaves.
  • Page 41: F = Parameters For Controlling The Evaporator Fans

    11.10 F = parameters for controlling the evaporator fans FAN PARAMETERS Type Max. Def. To LAN • Fan management: flag 0 = fan always ON (except in special cases: see parameters F2, F3, Fd) 1 = fans thermostat-controlled in accordance with the absolute set-point F1 °C/°F •…

  • Page 42: H = Other Settings

    11.11 H = other settings OTHER PRE-SETTINGS Type Max. Def. To LAN Serial address (only for the network Master) Relay 4 selection: flag 0 = auxiliary output 1 = alarm relay, normally open (closed in alarm) 2 = alarm relay, normally closed (open in alarm) 3 = auxiliary relay: Master serves the Slaves;…

  • Page 43
    • In = 0: unit configured as Slave — Available on all models — The default for this parameter depends on the model of the instrument; see the second row of the following table for the default values of the various models: IRMPX00000 IRMPX0M000 IRMPX0A000 IRMPX10000…
  • Page 44: Operating States Of The Units

    12. Operating states of the units As indicated above, the display LEDs can be in three states: • off, when the function indicated or the actuator is not operative; • on, when the function indicated or the actuator is operative; •…

  • Page 45
    13. Alarms 13.1 Defective or incorrect operation The units in the MPX range are able to signal most incorrect operations automatically. When a malfunction occurs, the microprocessor initiates the following actions: • the malfunction is signalled on the display by an appropriate alarm code. More specifically, the display shows the alarm code and the temperature read by the probe, alternating in sequence.
  • Page 46: Alarms

    HI FLASHING High temperature alarm. The probe has measured a temperature further above the set value than the value set for parameter AH. • Check parameters AH, Ad and A0. • The alarm will cease as soon as the temperature returns within the set limits (see parameter AH). EA, EB DISPLAYED DURING OPERATION OR WHEN SWITCHING-ON Data acquisition error.

  • Page 47: Troubleshooting

    14. Troubleshooting PROBLEM CAUSE CHECK compressor does not start : compressor delay in progress parameters c0, c1 and c2 • power on • compressor LED flashing temperature is outside set limits but no alarm alarm delay in progress check Ad signalled and the buzzer, if fitted, does not sound the AL or Ad alarm signalled (Multi-function…

  • Page 48: Technical Specifications

    15. Technical specifications 15.1 Technical characteristics: Probe type: NTC Carel Operating field: -55°c — +95°c ± 0.5°C Precision : Storage: -10°C/ 70°c Operating conditions: 0°C/+50°c Power supply: 12Vac Power consumption: 150mA Front panel index of protection: IP65 with panel mounted and gasket inserted…

  • Page 49: Temperature/Resistance Ratios For Ntc Thermistors

    Rmax is the maximum value. For the sake of simplicity, the values corresponding to only a limited number of temperatures are given. Intermediate values can be determined by interpolation. Temperature/Resistance ratios for the Carel NTC temperature probe Temperature Rmin Rstd Rmax -40 ºC…

  • Page 50: View Of The Instrument

    15.3 View of the instrument Dimensions of the MPX in mm: 25/06/01 Cod. +030220191 rel. 2.0 dated…

  • Page 51: Wiring Diagrams

    16. WIRING DIAGRAMS Master/Slave connection wiring diagram: Transformer Transformer Transformer (*) Insulating Transformer transformer Example of wiring for serial connection of the instruments: Main = mains power supply TRF = transformer INS TRF = insulating transformer = earth SER = multiple connection to the controller system 16.1 MPX contact rear view: Label of connections for the IRMPX10000 model (slave with 4 relays): Label of connections for the IRMPXM0000 model (Master with 485):…

  • Page 52: Summary Of Parameters

    17. Summary of parameters PARAMETER Type Min. Max. Def. To LAN 2 PASSWORD PARAMETERS LOG PASSWORD DOWNLOAD PASSWORD PROBE PARAMETERS Type Min. Max. Def. To LAN Temperature set-point °C/°F -10.0 • °C/°F Regulation probe calibration Measurement stability Probe reading rate •…

  • Page 53
    COMPRESSOR PARAMETERS Type Min. Max. Def. To LAN • Compressor start delay when the instrument is turned ON min. • Minimum time between two successive compressor starts min. • Minimum compressor off time min. • Minimum compressor on time min. •…
  • Page 54
    FAN PARAMETERS Type Min. Max. Def. To LAN • Fan management: flag 0 = fan always ON (except in special cases: see parameters F2, F3, 1 = fans thermostat-controlled in accordance with the absolute set- point F1 °C/°F • Fan start absolute set-point Active if F0 = 1 •…
  • Page 55
    Note: ___________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________…
  • Page 56
    Note: ___________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________…
  • Page 57
    Note: ___________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________…
  • Page 59
    Agency: CAREL srl Via dell’Industria, 11 — 35020 Brugine — Padova (Italy) Tel. (+39) 049.9716611 Fax (+39) 049.9716600 http://www.carel.com — e-mail: carel@carel.com…
  • Page 1: User Manual

    / easy compact / easy split electronic digital thermostats with defrost control User manual NO POWER & SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT! I n t e g r a t e d C o n t r o l S o l u t i o n s & E n e r g y S a v i n g s…

  • Page 3
    The technical specifi cations shown in the manual may be changed without prior warning. The liability of CAREL in relation to its products is specifi ed in the CAREL general contract conditions, available on the website www.carel.com and/or by specifi c agreements with customers; specifi cally, to the extent where allowed…
  • Page 5: Table Of Contents

    Content 1. INTRODUCTION 1.1 Main characteristics ………………..7 1.2 Models ……………………7 1.3 Main diff erences between easy, easy compact and easy split ..9 1.4 NTC and PTC probes ………………9 1.5 Accessories ………………….9 1.6 Defi nitions …………………..9 2. ASSEMBLY AND INSTALLATION 2.1 Assembly …………………..10 2.2 Electrical connections ………………11…

  • Page 7: Introduction

    1.1 Main characteristics The following table lists the main features of the easy, easy compact and easy split controllers. Features…

  • Page 8
     fan management with comp. off 4.10   night-time operation with light 4.11 management Table 1.b * available but cannot be set from the keypad nor the programming key. easy/easy compact/easy split +030220791 — rel. 3.2 — 13.07.2010…
  • Page 9: Main Diff Erences Between Easy, Easy Compact And Easy Split

    PTC, and 10 kΩ for the NTC. The type of probe installable depends on the model (order code). The easy split models, on the other hand, only use NTC and high temperature NTC probes (50 KΩ at 25°C), selected by parameter.

  • Page 10: Assembly And Installation

    (formation of corrosive patina with possible oxidation (*) do not over-tighten the screws. and reduction of insulation. To install easy, easy compact and easy split: make an opening in the panel based on the drilling template, 71×29 mm. Dismantling using the screws from the front •…

  • Page 11: Electrical Connections

    • the probes can be installed up to a maximum distance of 30 m from the controller (10 m for easy split). To extend the distance of the probes, 230Vac or use cables with a minimum cross-section of 1 mm2, shielded where…

  • Page 12
    (*) For codes PJEZ*8**5* the temperature range is -10T50 °C and the maximum current is 16 A. See the table of technical specifi cations. ———— = recommended internal power supply connections. easy/easy compact/easy split +030220791 — rel. 3.2 — 13.07.2010…
  • Page 13: Wiring Diagram For Multiple Units

    120 ohm Fig. 2.h easy split: The serial connection for the easy split models with 4 relays depends on the setting of parameter H7, as the management of the fourth relay (RL4) and serial communication are mutually exclusive. The factory setting is H7=1, which means the fourth relay is enabled. To enable connection to the supervisor network: power down the controller;…

  • Page 14: User Interface And Start Up

    EZY together (2 — more than 3 s: accesses and 3) activate Keypad functions for easy and easy compact M models the parameter setting menu parameter (models with keypad only) (enter password 22) reset — mutes the audible alarm…

  • Page 15: Easy Split

    Display the controller to make it operative. CAREL then recommends to check that the display does not show any alarm signals (see par. “5.1 Table of alarms and signals” on page 31), then set the time and date (in the models fi tted with RTC, see par. “4.11 Clock and time band parameters”…

  • Page 16
    Press DOWN for more than 3 s (activated only if the temperature conditions are right, for easy split only if the light output is not set, H1≠4). Alternatively, on easy split models, if the light output is set (H1=4), the defrost can be activated by pressing UP and DOWN together, when H6=1).
  • Page 17: Functions And Parameters

    This chapter describes all the functions of the easy, easy compact and Example: In the case of bottle coolers, typically used in supermarkets, easy split. See Table 1.b for the compatibility of the functions with the when the doors are opened frequently, due to the greater thermal inertia model used.

  • Page 18: Temperature Control

    Used to enable or disable the temperature display with the resolution to Value that automatically increases the set point temperature during the the tenths of a degree between -20 and + 20 (easy and easy split) or -10 night-time operation time bands.

  • Page 19: Continuous Cycle

    (H1=7). 4.6 Compressor protection The easy, easy compact and easy split controllers are fi tted with an automatic compressor protection system to avoid continual starts or stops of the unit. The protection is based on the times in minutes set for parameters c0;…

  • Page 20: Defrost

    • from the keypad pressing the DOWN button for 3 s (manual defrost) (for easy split H1 must be ≠4. If H1=4 the UP and DOWN buttons can be pressed together, when H6=1); dt: end defrost temperature set point/defrost temperature threshold •…

  • Page 21
    (only manual defrosts from the keypad or multifunction contact) or to set dI to a value which is greater than the maximum set interval. easy/easy compact/easy split +030220791 — rel. 3.2 — 13.07.2010…
  • Page 22: Alarm Parameters

    A4: 3rd input confi guration (easy compact) The multifunction input is only available on the easy models with three inputs; is not available on the easy compact models. A0: alarm and fan temperature diff erential This parameter is used to set the functions of the input.

  • Page 23
    (1) contact open= alarm detected unit 1 contact closed= normal operation. When A4=1 easy can be connected to an external contact for immediately dP (2) d5 (2) signalling alarms. The alarm signal can be delayed by setting parameter unit 2…
  • Page 24
    14 Product probe again). Table 4.o AC-AE/2 A4=0, 1, 2, 3: see A4=0, 1, 2, 3 for easy, easy compact in previous paragraph. AC-AE A4=4 Curtain switch and night-time operation See the previous paragraph. In easy split models if the light output is Fig.
  • Page 25: Door Open/Closed Management

    Door switch with evaporator fan off and light not managed A4=13 for easy split). See A4=7 for easy, easy compact in previous paragraph. In easy split models with light output confi gured (H1=4), the status of the light output remains unchanged.

  • Page 26
    Easy split Closing the door the fi rst time: the controller maintains the previous status: In easy split models the algorithm for managing the door depends on • the fans and/or compressor (see parameter ‘A4’) remain off ; the type of unit selected, according to parameter Ado, and the setting •…
  • Page 27: Evaporator Fan Management Parameters

    The evaporator fan control temperature is measured by probe 2, (connector 10). To know which output is associated with the fan, see the wiring diagram for the “easy” model used (see par. “2.2 Electrical connections” page 11). Important: these parameters are not available in the compact models.

  • Page 28: Clock And Time Band Parameters

    Parameters for setting up to 4 defrost time bands 4.11 Clock and time band parameters d1d…d4d Defrost event day setting The RTC (Real Time Clock), not available on the easy compact models, is d1d…d4d=0 no defrost event used to manage the defrost function, curtain switch/night-time operation d1d…d4d=1…7 Monday to Sunday…

  • Page 29: Rapid Parameter Set Selection (Ezy)

    Examples of operation: the digital input. On easy split models there are also the light and second compressor outputs, with or without rotation. example 1…

  • Page 30
    When set to a positive value (values from 0 to 31 are used REQ2 by CAREL for the basic models), if a parameter, including the set point, is modifi ed from the keypad, the value becomes negative. This allows any modifi cations made the parameters compared to the initial settings to be monitored.
  • Page 31: Tables Of Alarms And Parameters

    5. TABLES OF ALARMS AND PARAMETERS 5.1 Table of alarms and signals Note: in easy split controllers, when starting control (powering up When an alarm is activated, the display shows the corresponding message the controller and/or switching from OFF status), the high that fl ashes alternating with the temperature;…

  • Page 32: Data Error

    • press the SET button for more than 3 s to permanently save the parameters and exit the parameter setting procedure. easy/easy compact/easy split +030220791 — rel. 3.2 — 13.07.2010…

  • Page 33: Table Of Easy Parameters

    X, Y, C (*) AUX time band ON day days X, Y, C (*) AUX time band ON hours X, Y, C (*) AUX time band ON minutes X, Y, C (*) easy/easy compact/easy split +030220791 — rel. 3.2 — 13.07.2010…

  • Page 34: Table Of Easy Compact Parameters

    S (with 1 & 2 probes) Table 5.d Warning Warning the easy compact models only display two digits. If the range is below -99 and above 99, the terminal will display “- — “. easy/easy compact/easy split +030220791 — rel. 3.2 — 13.07.2010…

  • Page 35: Table Of Easy Split Parameters

    S,C (*) night time band ON day S,C (*) night time band ON hours S,C (*) nOM night time band ON minutes S,C (*) night time band OFF day S,C (*) easy/easy compact/easy split +030220791 — rel. 3.2 — 13.07.2010…

  • Page 36: Table Of Ezy Parameter Sets

    (reverse) digital input alarm management defrost with temp. control (d0= 4) defrost by temperature (d0=4) easy/easy compact/easy split +030220791 — rel. 3.2 — 13.07.2010…

  • Page 37
    (reverse) digital input alarm management defrost with temp. control (d0= 4) defrost by temperature (d0=4) easy/easy compact/easy split +030220791 — rel. 3.2 — 13.07.2010…
  • Page 38: Troubleshooting

    • F1 (evaporator fan control set point) too low. • post-dripping delay set 3. if F0=0 • F2=1 and the compressor is off • dripping in progress • post-dripping in progress Table 5.i easy/easy compact/easy split +030220791 — rel. 3.2 — 13.07.2010…

  • Page 39: Technical Specifications

    Warning : do not run the power cable less than 3 cm from the bottom of the device or the probes; for the connections, only use Fig. 6.b copper wires. 65,29 71×29 Fig. 6.a easy/easy compact/easy split +030220791 — rel. 3.2 — 13.07.2010…

  • Page 40: Easy Split Technical Specifi Cations

    (**) Minimum T OFF between two starts must be greater than 1 min. (***) Conformity to UL873 only corresponds to models without plastic case. Terminal Power board 103.5 Ø 4 38,29 71×29 Fig. 6.c Fig. 6.d easy/easy compact/easy split +030220791 — rel. 3.2 — 13.07.2010…

  • Page 41: Electromagnetic Compatibility

    6.4 Electromagnetic compatibility The easy and easy compact series is compliant with the EU standards on electromagnetic compatibility: • for household appliances EN 55014-2 and EN 55014-1; • for residential, commercial and light industrial environments EN 50082-1 and EN 50081-1;…

  • Page 42
    Notes…
  • Page 44
    Agenzia / Agency: CAREL INDUSTRIES — HQs Via dell’Industria, 11 — 35020 Brugine — Padova (Italy) Tel. (+39) 049.9716611 — Fax (+39) 049.9716600 e-mail: carel@carel.com — www.carel.com…

Посмотреть инструкция для Carel MPXPRO бесплатно. Руководство относится к категории без категории, 5 человек(а) дали ему среднюю оценку 8.8. Руководство доступно на следующих языках: русский. У вас есть вопрос о Carel MPXPRO или вам нужна помощь? Задайте свой вопрос здесь

Не можете найти ответ на свой вопрос в руководстве? Вы можете найти ответ на свой вопрос ниже, в разделе часто задаваемых вопросов о Carel MPXPRO.

Инструкция Carel MPXPRO доступно в русский?

Да, руководствоCarel MPXPRO доступно врусский .

Не нашли свой вопрос? Задайте свой вопрос здесь

Понравилась статья? Поделить с друзьями:
  • Mql4 ошибка 129
  • Mprint lp58 eva ошибка печати
  • Mortal kombat ошибка открытия
  • Mscorwks dll windows 7 ошибка
  • Mortal kombat ошибка msvcr110 dll