[7-3 Error Code Definitions and Solutions: Codes [1000 — 1999] ]
7-3-4
1. Error code definition
High pressure fault 2 (Outdoor unit)
2. Error definition and error detection method
If the pressure of 0.098MPa [14psi] or lower is registered on the pressure sensor immediately before start-up, it will trigger an
abnormal stop, and error code «1302» will be displayed.
3. Cause, check method and remedy
(1)
Inner pressure drop due to a leakage.
(2)
Pressure sensor failure
(3)
Shorted-circuited pressure sensor cable due to torn
outer rubber
(4)
A pin on the male connector on the pressure sensor
is missing or contact failure
(5)
Disconnected pressure sensor cable
(6)
Failure of the pressure sensor input circuit on the
controller board
7-3-5
Error Code [1500]
1. Error code definition
Refrigerant overcharge
2. Error definition and error detection method
An error can be detected by the discharge temperature superheat.
1) If the formula «TdSH
10°C [18°F]» is satisfied during operation (first detection), the outdoor unit stops, goes into the 3-minute
restart mode, and starts up in three minutes.
2) If the formula «TdSH
10°C [18°F]» is satisfied again within 30 minutes of the first stoppage of the outdoor unit (second de-
tection), the unit comes to an abnormal stop, and the error code «1500» appears.
3) If the formula «TdSH
10°C [18°F]» is satisfied 30 minutes or more after the first stoppage of the outdoor unit, the same se-
quence as Item «1 above (first detection) is followed.
4) For 30 minutes after the stop of the outdoor unit, preliminary errors will be displayed on the LED display.
3. Cause, check method and remedy
(1)
Overcharged refrigerant
(2)
Thermistor input circuit failure on the control board
(3)
Faulty mounting of thermistor (TH4)
(4)
Solenoid valve actuation failure (SV5b)
(5)
Solenoid valve actuation failure (SV4a, SV4b, or
SV4d)
→ Heating only or heating main
(6)
LEV5a failure→ Heating only or heating main
(7)
LEV4 failure→ Heating only or heating main
HWE13080
Cause
Cause
Check method and remedy
Refer to the following page(s). [8-5-1 Comparing the
High-Pressure Sensor Measurement and Gauge
Pressure](page 267)
Check method and remedy
Refer to the following page(s). [6-9 Evaluating and Adjust-
ing Refrigerant Charge](page 161)
Check the temperature and pressure readings on the sen-
sor that are displayed on the LED monitor.
Check the temperature and pressure readings on the
thermistor that are displayed on the LED monitor.
Perform a cooling or heating operation and check the oper-
ation.
[8-8 Troubleshooting LEV Problems](page 273)
— 183 —
GB
Поддержание оптимальной температуры в комнате необходимо для комфортных условий. Когда
кондиционер ломается, жаркая погода может испортить весь день, потому что заставит
чувствовать себя неприятно. Следует определить код ошибки кондиционеров и провести
дальнейшую диагностику, чтобы вернуть устройство к работе.
Как определяются коды ошибки кондиционеров Mitsubishi Electric
Для того чтобы считать коды ошибок кондиционеров Mitsubishi Electric, воспользуйтесь
инструкцией производителя, а затем расшифруйте код при помощи таблицы:
P1 | Неисправность датчика температуры ТН3 |
Р2 | Неисправность датчика, считывающего данные TH5-теплообменника |
Р4 | Дренажный поддон наполнен выше нормы (также возможна неисправность датчика-поплавка CN4F) |
Р5 | Неисправность помпы, установленной в дренажном отсеке |
Р6 | Неправильное выполнение команды понижения или повышения температуры |
Р8 | Неправильная температура установилась в теплообменнике |
Р9 | Неисправность датчика, считывающего данные ТН2-теплообменника |
РА | Компрессор был аварийно и принудительно остановлен |
Е0 | Невозможна передача сигнала к пульту управления |
Е1 | Кнопки на пульте управления неисправны |
Е2 | Адреса внутренних систем дублированы |
Е3 | Адрес наружного блока указан неправильно |
Е4; Е5 | Приемник сигнала с пульта управления неисправен |
Е6 | Есть замыкание в соединении внутреннего и внешнего блока |
Е7 | Ошибка передачи данных в системе |
Е8 | Обрыв цепи около датчика приема данных |
Е9 | Не получается связаться с передатчиком |
Е0 | Низкий заряд батареи пульта |
ЕА | Неправильная установка электросети и соединений проводов |
ЕВ | Защита электросети от перенапряжения |
ЕС | Не получилось запустить работу системы по таймеру |
Ed | Необходимо сбросить все до базовых настроек |
ЕЕ | Невозможно передать данные на передатчик |
EF | M-NET ошибка – неправильное соединение проводов |
U1 | Датчик 63Н указывает на давление выше нормы (либо температуру выше нормы) |
U1 | Фатальная ошибка |
U2 | Датчик 49С говорит о низком давлении при заборе воздуха или низком уровне хладагента |
U2 | Компрессор работает на высокой температуре |
U3 | Варистор конденсатора неисправен |
U4 | В электросети датчика температуры внешнего блока есть обрыв или короткое замыкание |
U5 | Датчик температуры конденсатора сигнализирует о превышении нормы |
U6 | Обнаружена токовая перегрузка электросети компрессора, устройство остановлено |
U7 | Датчик 49С указывает на ошибку |
U8 | Принудительная остановка моторчика вентилятора, установленного во внешнем блоке |
U9; UH | Отклонение от нормы напряжения электрического тока, поступающего от сети, ошибка в показаниях датчика напряжения тока |
UA | Ошибка пускового реле компрессора |
UD | Компрессор перегрелся |
UL | Низкое давление хладагента |
UF | Слишком высокий уровень напряжения, остановка компрессора |
UP | Перегрузка электросети, принудительная остановка компрессора |
Fb | Ошибка системы программирования |
F1 | Нет данных от датчика температуры ТН3 |
F2 | Обрыв фазы на участке L3 |
F3 | Неправильное соединение с внутренней платой управления – нет сигнала |
F4 | Разомкнулся разъем |
F7 | Нарушена последовательность в фазах шлейфа |
F8 | Нестабильное напряжение сети |
F9 | Нет сигнала в разъемах |
FA | Обрыв фазы на участках L2 |
Ошибки кондиционеров Mitsubishi Electric на пульте ДУ
Е0 | Не получается передать команду на кондиционер |
Р1 | Данные о всасываемом воздухе считываются неправильно |
Р2 | Неисправность трубочек |
Р3 | Системная ошибка |
Р4 | Нет данных от датчика Drain |
Р5 | Утечка переполнения защиты механизма |
Р6 | Неправильно проведено снижение или увеличение температуры |
Р7 | Системная ошибка (формирование данных) |
Р8 | Обрыв соединения |
LED лампы
Статус операции | Проверка выдачи кода ошибки |
---|---|
LD1 | Компрессор |
LD2 | Регулировка температуры |
LD3 | Проведение операции 63Н3 |
LD4 | Компрессор работает во время операции 63Н2 |
LD5 | Включен вентилятор |
LD6 | Работает четырехходовой клапан |
LD7 | Перепускной клапан |
LD8 | Работает нагреватель картера |
Индикация светодиода | |
Вспышка раз в 2 секунды | Неисправно питание конвертора, внешнее питание, термистор или система управления наружного блока |
Две вспышки раз в 2 секунды | Защита от короткого замыкания |
Три вспышки раз в 2 секунды | Защита от превышения нормальной температуры системы нагнетания |
Четыре вспышки раз в 2 секунды | Защита от превышения нормальной температуры термистора |
Пять вспышек раз в 2 секунды | Защита от превышения нормы давления в системе |
Семь вспышек раз в 2 секунды | Защита от случайного старта системы |
Восемь вспышек раз в 2 секунды | Защита ошибки в установке температуры |
Одна вспышка | Снизилось напряжение в электросети |
Три вспышки | Сработал режим размораживания |
Четыре вспышки | Высокая температура системы нагнетания |
Пять вспышек | Термистор наружный |
Семь вспышек | Низкая температура системы нагнетания |
Восемь вспышек | Конвертор защищается |
Девять вспышек | Инвертор проверяется |
Error | Расшифровка | Русский перевод |
P1 | Intake sensor error | Ошибка датчика на входе |
P2 | Pipe (TH5) sensor error | Ошибка датчика теплообменника ТН5 (по схеме) |
P4 | Drain sensor error/Float switch connector (CN4F) open | Переполнение дренажного поддона, или обрыв поплавкового датчика CN4F |
P5 | Drain pump error | Ошибка дренажной помпы |
P6 | Freezing/Overheating protection operation | Ошибка по обмерзанию или перегреву |
P8 | Pipe temperature error | |
P9 | Pipe (TH2) sensor error | Ошибка по датчику теплообменника ТН2 |
PA | Forced compressor stop(due to water leakage abnormality) | Принудительная остановка компрессора (из-за переполнения дренажной системы) |
E0, E3 | Remote controller transmission error | Нет связи с пультом управления |
E1, E2 | Remote controller control board error | Неисправна плата пульта управления |
E4, E5 | Remote controller signal receiving error | |
E9 | Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit) | Нет связи между внутренним и внешним блоком (Ошибка на внешнем блоке) |
EE | Communication error between indoor and outdoor units | Отсутствует межблочная связь между внутренним и внешним блоками |
U1,Ud | Abnormal high pressure (63H worked)/Overheating protection operationс | Высокое давление по датчику 63Н, или защита от перегрева |
U2 | Abnormal high discharging temperature/49C worked/insufficient refrigerant | Сработал датчик 49С, очень низкое давление нагнетания, недостаток хладагента |
U3, U4 | Open/short of outdoor unit thermistors | Обрыв, короткое замыкание термодатчика внешнего блока |
U5 | Abnormal temperature of heat sink | Температура конденсатора не соответствует норме |
U6 | Compressor overcurrent interruption/Abnormal of power module | Компрессор принудительно остановлен по токовой перегрузке, неисправен силвой модуль |
U7 | Abnormality of super heat due to low discharge temperatureAbnormal high discharging temperature/49C worked/insufficient refrigerant | Сработал датчик 49С / очень низкое давление нагнетания / недостаток хладагента |
U8 | Outdoor unit fan protection stop | Двигатель вентилятора внешнего блока остановлен |
U9, UH | Abnormality such as overvoltage or voltage shortage and abnormal synchronous signal to main circuit/Current sensor error | Повышенное / пониженное напряжение питания, неисправность токового датчика |
UF | Compressor overcurrent interruption (When compressor locked) | Компрессор остановлен из-за токовой перегрузки, компрессор заклинило |
UP | Compressor overcurrent interruption | Остановка компрессора из-за перегрузки по току |
Fb | Indoor unit control system error (memory error, etc.) | Ошибка платы управления внутреннего блока (EEPROM и т.д.) |
Определить ошибку в бытовых сплит системах можно по миганию индикаторов на панели внутреннего блока.
Получить расшифровку всех возможных кодов холодильного оборудования Mitsubishi Electric можно на сайте:
Язык оригинальной документации — английский.
Компания Mitsubishi Electric разработала программу для телефонов с помощью которой можно получить расшифровку кода ошибок.
As an Amazon affiliate, we earn a commision from qualifying purchases.
Mitsubishi City Multi VRF air conditioning systems are famed for their ultra-quiet noise levels, higher savings on installation and running costs, and a significantly reduced footprint.
But much like other air conditioner brands, your mitsubishi city multi air conditioner may, on occasion, malfunction.
Now, a good place to start your troubleshooting when a fault occurs is looking for error codes- and the great thing is that some of the most common mitsubishi city multi error codes can be resolved by performing basic DIY maintenance.
This article lists the most prevalent mitsubishi city multi error codes and their meaning- plus tips to help you fix the problem depending on the exact model you own.
Read through the fault codes- solving the problem causing your air conditioner not to operate properly may be a lot easier than you think:
With many mitsubishi city multi air conditioner models, fault codes are made up of 3 or 4 digits.
Here is a detailed list of mitsubishi city multi error codes, possible meanings, and potential troubleshooting steps (for some):
Mitsubishi City Multi Error Codes- full list
Error code 403 (Mitsubishi City Multi R22, R4O7c, and R410A models)
Meaning: Communication fault between boards
Recommended fix: Check transformer, bus voltage, and inter-connecting cables. Also check inverter error detail for which 2 boards.
Error code 1102 (Mitsubishi City Multi R22, R4O7c, and R410A models)
Meaning: Compressor discharge temperature high (has exceeded 110°C).
Recommended fixes: refrigerant may need to be refilled (could be insufficient). In addition, check discharge thermistor.
Mitsubishi city multi error code 1111, 1112, 1113 (Mitsubishi City Multi R22, R4O7c)
Meaning: Low pressure/temperature problem
Recommended fixes: check thermistors (TH2, TH3, TH4). Also check gas charge, the indoor fan, heat exchanger, and filter
Error code 1202 (Mitsubishi City Multi R22, R4O7c, R410A)
Meaning: Preliminary fault to error code 1102
Error code 1204 (Mitsubishi City Multi R410A)
Meaning: Preliminary heat exchanger gas temperature sensor problem
Recommended fixes: check thermistors 10a & 10b
Error code 1205 (Mitsubishi City Multi R22, R4O7c, R410A)
Meaning: Preliminary thermistor issue(TH5)
Error code 1211 (Mitsubishi City Multi R22, R4O7c)
Meaning: Preliminary thermistor issue(TH2)
Error code 1214 (Mitsubishi City Multi R22, R4O7c, R410A)
Meaning: Preliminary thermistor issue(THHS)
Error code 1216 (Mitsubishi City Multi R22, R4O7c, R410A)
Meaning: Preliminary thermistor issue(TH7)
Error code 1217 (Mitsubishi City Multi R22, R4O7c, R410A)
Meaning: Preliminary thermistor issue(TH8)
Error code 1219 (Mitsubishi City Multi R22, R4O7c)
Meaning: Preliminary thermistor issue(TH9)
Error code 1221 (Mitsubishi City Multi R22, R4O7c, R410A)
Meaning: Preliminary thermistor issue(TH6)
Error code 1243 (Mitsubishi City Multi R4O7c)
Meaning: Preliminary thermistor issue(TH10)
Error code 1301 (Mitsubishi City Multi R4O7c)
Meaning: Low pressure fault(63L operation)-low pressure sensor could be sensing less than 1 bar immediately before starting.
Error code 1302 (Mitsubishi City Multi R22, R4O7c)
Meaning: High pressure issue – check pressure in the system for more than 29 bar(R407c)/38 bar(R410A).
Recommended fixes: Check the high pressure sensor against the gauge pressure
Error code 1368 (Mitsubishi City Multi R22, R4O7c)
Meaning: Pressure sensor issue(PS1) at BC
Recommended fixes: Compare the pressure reading on SW1 (on O/C)
Error code 1370 (Mitsubishi City Multi R22, R4O7c)
Meaning: Pressure sensor fault(PS3) at BC
Recommended fixes: compare the pressure reading on SW1(at O/C)
Error code 1402(Mitsubishi City Multi R410A)
Meaning: Preliminary issue to 1302
Error code 1500 (Mitsubishi City Multi R22, R4O7c, R410A)
Meaning: System overcharge(Abnormal low compressor super-heat ).
Recommended fixes: discharge thermistor TH4
Error code 1501 (Mitsubishi City Multi R22, R4O7c)
Meaning: High compressor shell temperature
Recommended fixes: check for potential shortage of gas. Can also be due to insufficient indoor index running(comms room units).
Error code 1505 (Mitsubishi City Multi R22, R4O7c)
Meaning: Abnormal suction pressure(generated when low pressure sensor detects a vacuum)
Recommended fixes: check for blockage or a closed valve. Also check for sensor fault
Error code 2500 (Mitsubishi City Multi R22, R4O7c, R410A)
Meaning: there is lack of waterflow on the water circuit
Mitsubishi city multi error code 2502 (R22, R4O7c, R410A)
Meaning: I/C has water level in the drip tray
Troubleshooting steps: check for open/closed circuit(temperature sensors). Also check if the pump is operating correctly.
Error code 2503 (R22, R4O7c, R410A)
Meaning: I/C has water level in the drip tray
Troubleshooting steps: check for closed circuit(on float switch). Also check if the pump is running properly.
Error code 2600 (R22, R410A)
Meaning: Water is leaking from humidifier
Error code 4102 ( R410A)
Meaning: Open phase fault
Troubleshooting steps: Check the power supply as well as noise filter for possible loss of phase. Also check the wiring and fuses.
Error code 4103 (R22, R4O7c, R410A)
Meaning: Reverse phase issue.
Troubleshooting steps: -check phase rotation. Also check if there is loss of phase (through noise filter). Finally check if there is a blown fuse or if the high pressure switch is open (at power on)
Error code 4108 ( R410A)
Meaning: Over current protection (on DOL compressor)
Troubleshooting steps: Check the following parts: power supply, contactor, and compressor
Error code 4115 (R22, R4O7c, R410A)
Meaning: power supply abnormal
Troubleshooting steps: – check power, connections, fuses, and PCB
Error code 4116 (R22, R4O7c, R410A)
Meaning: Fan motor abnormal
Troubleshooting steps: check fan motor as well as the board (relates to the indoor unit/Lossnay unit)
Error code 4210 ( R22)
Meaning: Compressor over current fault
Troubleshooting steps: check the inverter balance. Also check the compressor and inverter.
Error code 4220 (R4O7c, R410A)
Meaning: Low BUS voltage on inverter board (Less than 289VdcDC detected).-
Troubleshooting steps: check mains supply
Error code 4225 (R410A)
Meaning: Low DC voltage detected on Vdc on the fan inverter
Troubleshooting steps: check the CNVdc for 300Vdc (on diode stack). Also check power supply(mains) to your outdoor unit
Error code 4230 (R22, R4O7c, R410A)
Meaning: High temp on heat sink (on inverter)
Troubleshooting steps: check for blockages (in air duct). Also check if the INV fan has failed. Finally test if the thermistor has failed.
Error code 4235 (R410A)
Meaning: Fan inverter heat sink overheating protection due to reduced airflow through the heat sink or a fan motor fault. This could also indicate THHS thermistor issue.
Error code 4240 (R22, R4O7c, R410A)
Meaning: Over current protection- high current may have been detected for 10 (or more) minutes.
Possible fixes: check inverter balance. Also try to identify what may be causing reduced airflow through the heat sink
Error code 4245 (R410A)
Meaning: Over current protection due to potential ACCT current sensor problem (Should read 280ohms between pins 1 and 2 and across the pins 3 and 4.
Error code 4250 (R410A)
Meaning: Over current protection (may be caused by Inverter IPM fault/Compressor lock)
Troubleshooting steps: check inverter balance
Error code 4255 (R410A)
Meaning: Inverter cooling fan issue.
Troubleshooting steps: if using high static fan, you should check that the SW3-9 is on.
Error code 4260 (R4O7c, R410A)
Meaning: Preliminary overheat protection (on inverter heat sink) probably caused by reduced airflow through the heat sink. The issue can also be due to a fan motor problem or THHS thermistor fault.
Error code 5101, 5102, 5103, 5104 (R22, R4O7c, R410A)
Meaning:Thermistor fault (at indoor/outdoor unit)
Troubleshooting steps: check error code address
Error code 5105 (R22, R4O7c, R410A)
Meaning:TH5 open/short circuit
Troubleshooting steps: The TH may be disconnected from the board. Check.
Error code 5106 (R22, R4O7c, R410A)
Meaning:TH6 open/short circuit
Troubleshooting steps: The TH may be disconnected from the board. Check.
Error code 5107 (R22, R4O7c, R410A)
Meaning:TH7 open/short circuit
Troubleshooting steps: The TH may be disconnected from the board. Check.
Error code 5108 (R22, R4O7c)
Meaning:TH8 open/short circuit
Troubleshooting steps: The TH may be disconnected from the board. Check.
Error code 5109 (R4O7c)
Meaning:TH9 open/short circuit
Troubleshooting steps: The TH may be disconnected from the board. Check.
Error code 5110 (R22, R4O7c, R410A)
Meaning:TH10 open/short circuit
Troubleshooting steps: The TH may be disconnected from the board. Check.
Error code 5111 (R22, R410A)
Meaning: BC box thermistor fault (due to TH11 open/short circuit or disconnection from board/pipe)
Error code 5112 (R22, R4O7c, R410A)
Meaning: BC box thermistor fault (due to TH10 open/short circuit or disconnection from board/pipe)
Error code 5113 (R22), Error code 5114 (R22)
Meaning: BC box thermistor fault (due to TH open/short circuit or disconnection from board/pipe)
Error code 5115 (R22, R410A)
Meaning: BC box thermistor fault (due to TH15 open/short circuit or disconnection from board/pipe)
Error code 5116 (R22, R410A)
Meaning: BC box thermistor fault (due to TH16 open/short circuit or disconnection from board/pipe)
Error code 5201 (R22, R4O7c, R410A)
Meaning: Pressure sensor problem (outdoor unit or BC box)
Troubleshooting steps: check error code address or SW 1 pressure sensor readings.
Error code 5202 (R22)
Meaning: Pressure sensor problem (PS2) in BC box
Error code 5203 (R22, R4O7c, R410A)
Meaning: Pressure sensor problem (outdoor unit or BC box)
Troubleshooting steps: check error code address or SW 1 pressure sensor readings.
Error code 5301 (R4O7c, R410A)
Meaning: Current sensor fault (or ACCT/DCCT)
Troubleshooting steps: check inverter error details
Error code 5401 (R410A)
Meaning:Temperature sensor fault
Troubleshooting steps: check CN 30 for humidity sensor
Error code 5701 (R410A)
Meaning: float switch connector loose
Troubleshooting steps: check switch. Also check CN4F (on the indoor unit)
Error code 6201 (R410A)
Meaning: TB7 transmission line has communication error
Troubleshooting steps: check for abnormality in voltage/short
Error code 6202 (R410A)
Meaning: Transmission processor hardware fault
Troubleshooting steps: check for short/noise on M-Net cable
Error code 6600 (R22, R4O7c, R410A)
Meaning: Repeat address issue -it means the same address has been assigned two (or more units)
Troubleshooting steps: the repeated address need to be corrected
Error code 6601 (R410A)
Meaning: Polarity setting fault (there is no voltage –or there is a short circuit -on m-net transmission line)
Error code 6602 (R22, R4O7c, R410A)
Meaning: Hardware error on transmission processor. It may also indicate noise interference or even a polarity problem on TB 7.
Error code 6603 (R22, R4O7c, R410A)
Meaning: Bus circuit busy.
Troubleshooting steps: check if the indoor unit (or anything else) is wired into TB7 (instead of TB3) and correct the wiring error
Mitsubishi city multi error code 6607 /mitsubishi vrf error code 6607 (R22, R4O7c, R410A)
Meaning: Communication issue (no response is coming from unit whilst the system is operational)
Error code 6608 (R22, R4O7c, R410A)
Meaning: Communication error -there is loss of voltage (or noise) entering into the transmission line
Error code 6831 (R410A)
Meaning:MA R/C communication fault
Troubleshooting steps: check connections on TB 15. You can also check that the controller had been removed while the I /C was powered
Error code 6832, 6833, 6834 (R410A)
Meaning:MA controller communication fault
Troubleshooting steps: check cable length – should not be bigger than 500m. Also, check for proper connection and that the proper type of cable has been used.
Error code 7100 (R22, R4O7c, R410A)
Meaning: Over capacity
Error code 7101 (R22, R4O7c, R410A)
Meaning: Capacity setting issue – SW2 set wrong (on indoors), SW5 set wrong on YHMA outdoor (SW3-10 on older kits)
Mitsubishi city multi error code 7102 (R22, R4O7c, R410A)
Meaning: It may point to an error in the number of units you have connected or indicate loss of MNet voltage (short/break). It may also mean there is no power to the BC or even wrong SW 5 setting on box (or even wrong box type).
Error code 7105 (R22, R4O7c, R410A)
Meaning: Address setting issue – OC/BC addressed incorrectly
Error code 7106 (R4O7c, R410A)
Meaning: Attribute setting fault (SW3-1 setting on GUF)
Error code 7107 (R4O7c, R410A)
Meaning: Port setting issue- check if there is too much capacity on one port. Also check wiring, SW2 setting, SW14 setting (it could be wrong too) or even for wrong units (on a box if using multiple boxes)
Wrap up
This ‘mitsubishi city multi error codes check list’ provides an easy-to-use reference guide on all mitsubishi city multi error codes across the company’s product range.
More troubleshooting ideas and guidance can be found on the trouble-shooting section of your specific model’s service manual.
Be sure to contact a qualified HVAC technician if your aircon need advanced repair(s).
RELATED:
LG mini split error codes and troubleshooting guide
Trane thermostat error codes – comprehensive
- 16 мая, 2018
- Нет комментариев
Коды ошибок кондиционеров Mitsubishi Electric
Поддержание оптимальной температуры в комнате необходимо для комфортных условий. Когда
кондиционер ломается, жаркая погода может испортить весь день, потому что заставит
чувствовать себя неприятно. Следует определить код ошибки кондиционеров и провести
дальнейшую диагностику, чтобы вернуть устройство к работе. (Коды ошибок кондиционеров Mitsubishi Electric)
Как определяются коды ошибки кондиционеров Mitsubishi Electric
Для того чтобы считать коды ошибок кондиционеров Mitsubishi Electric, воспользуйтесь
инструкцией производителя, а затем расшифруйте код при помощи таблицы:
P1 Неисправность датчика температуры ТН3
Р2 Неисправность датчика, считывающего данные TH5-теплообменника
Р4 Дренажный поддон наполнен выше нормы (также возможна неисправность датчика-поплавка CN4F)
Р5 Неисправность помпы, установленной в дренажном отсеке
Р6 Неправильное выполнение команды понижения или повышения температуры
Р8 Неправильная температура установилась в теплообменнике
Р9 Неисправность датчика, считывающего данные ТН2-теплообменника
РА Компрессор был аварийно и принудительно остановлен
Е0 Невозможна передача сигнала к пульту управления
Е1 Кнопки на пульте управления неисправны
Е2 Адреса внутренних систем дублированы
Е3 Адрес наружного блока указан неправильно
Е4; Е5 Приемник сигнала с пульта управления неисправен
Е6 Есть замыкание в соединении внутреннего и внешнего блока
Е7 Ошибка передачи данных в системе
Е8 Обрыв цепи около датчика приема данных
Е9 Не получается связаться с передатчиком
Е0 Низкий заряд батареи пульта
ЕА Неправильная установка электросети и соединений проводов
ЕВ Защита электросети от перенапряжения
ЕС Не получилось запустить работу системы по таймеру
Ed Необходимо сбросить все до базовых настроек
ЕЕ Невозможно передать данные на передатчик
EF M-NET ошибка – неправильное соединение проводов
U1 Датчик 63Н указывает на давление выше нормы (либо температуру выше нормы)
U1 Фатальная ошибка
U2 Датчик 49С говорит о низком давлении при заборе воздуха или низком уровне хладагента
U2 Компрессор работает на высокой температуре
U3 Варистор конденсатора неисправен
U4 В электросети датчика температуры внешнего блока есть обрыв или короткое замыкание
U5 Датчик температуры конденсатора сигнализирует о превышении нормы
U6 Обнаружена токовая перегрузка электросети компрессора, устройство остановлено
U7 Датчик 49С указывает на ошибку
U8 Принудительная остановка моторчика вентилятора, установленного во внешнем блоке
U9; UH Отклонение от нормы напряжения электрического тока, поступающего от сети, ошибка в показаниях датчика напряжения тока
UA Ошибка пускового реле компрессора
UD Компрессор перегрелся
UL Низкое давление хладагента
UF Слишком высокий уровень напряжения, остановка компрессора
UP Перегрузка электросети, принудительная остановка компрессора
Fb Ошибка системы программирования
F1 Нет данных от датчика температуры ТН3
F2 Обрыв фазы на участке L3
F3 Неправильное соединение с внутренней платой управления – нет сигнала
F4 Разомкнулся разъем
F7 Нарушена последовательность в фазах шлейфа
F8 Нестабильное напряжение сети
F9 Нет сигнала в разъемах
FA Обрыв фазы на участках L2
Ошибки кондиционеров Mitsubishi Electric на пульте ДУ
Е0 Не получается передать команду на кондиционер
Р1 Данные о всасываемом воздухе считываются неправильно
Р2 Неисправность трубочек
Р3 Системная ошибка
Р4 Нет данных от датчика Drain
Р5 Утечка переполнения защиты механизма
Р6 Неправильно проведено снижение или увеличение температуры
Р7 Системная ошибка (формирование данных)
Р8 Обрыв соединения
LED лампы
Статус операции
Проверка выдачи кода ошибки
LD1 Компрессор
LD2 Регулировка температуры
LD3 Проведение операции 63Н3
LD4 Компрессор работает во время операции 63Н2
LD5 Включен вентилятор
LD6 Работает четырехходовой клапан
LD7 Перепускной клапан
LD8 Работает нагреватель картера
Индикация светодиода
Вспышка раз в 2 секунды Неисправно питание конвертора, внешнее питание, термистор или система управления наружного блока
Две вспышки раз в 2 секунды Защита от короткого замыкания
Три вспышки раз в 2 секунды Защита от превышения нормальной температуры системы нагнетания
Четыре вспышки раз в 2 секунды Защита от превышения нормальной температуры термистора
Пять вспышек раз в 2 секунды Защита от превышения нормы давления в системе
Семь вспышек раз в 2 секунды Защита от случайного старта системы
Восемь вспышек раз в 2 секунды Защита ошибки в установке температуры
Одна вспышка Снизилось напряжение в электросети
Три вспышки Сработал режим размораживания
Четыре вспышки Высокая температура системы нагнетания
Пять вспышек Термистор наружный
Семь вспышек Низкая температура системы нагнетания
Восемь вспышек Конвертор защищается
Девять вспышек Инвертор проверяется