Код ошибки 1102 mitsubishi electric

7-3

Error Code Definitions and Solutions: Codes [1000 — 1999]

7-3-1

Error Code [1102]

1. Error code definition

Discharge temperature fault

2. Error definition and error detection method

1) If the discharge temperature of 120 °C [248°F] or more is detected during the above operation (the first detection), the outdoor

unit stops once, turns to anti-restart mode for 3 minutes, and restarts after 3 minutes automatically.

2) If the discharge temperature of 120° C [248°F] or more is detected again (the second detection) within 30 minutes after the

second stop of the outdoor unit described above, the mode will be changed to 3 — minute restart mode, then the outdoor unit

will restart in 3 minutes.

3) If the discharge temperature of 120°C [248°F] or more is detected (the 30th detection) within 30 minutes after the stop of the

outdoor unit described above (regardless of the first or the 29th stop), the outdoor unit will make an error stop, and the error

code «1102» will be displayed.

4) If the discharge temperature of 120°C [248°F] or more is detected more than 30 minutes after the previous stop of the outdoor

unit, the detection is regarded as the first detection, and the operation described in step 1 above will start.

5) For 30 minutes after the stop (the first stop or the second stop) of the outdoor unit, preliminary errors will be displayed on the

LED display.

3. Cause, check method and remedy

(1)

Gas leak, gas shortage

(2)

Overload operation

(3)

LEV failure on the indoor unit

(4)

Outdoor unit LEV1 actuation failure

Outdoor unit LEV2 actuation failure

(5)

Closed refrigerant service valve

(6)

Outdoor fan (including fan parts) failure, mo-

tor failure, or fan controller malfunction

Rise in discharge temp. by low pressure

drawing for (3) — (6).

(7)

Gas leak between low and high pressures

(4-way valve failure, Compressor failure, So-

lenoid valve (SV1a) failure)

(8)

Thermistor failure

(TH4)

(9)

Input circuit failure on the controller board

thermistor

HWE14040

Cause

Check method and remedy

Refer to the following page(s).[6-9 Evaluating and Adjusting

Refrigerant Charge](page 131)

Check operating conditions and operation status of indoor/

outdoor units.

Perform a cooling or heating operation to check the opera-

tion.

Cooling: Indoor unit LEV, LEV1, LEV2

Heating: Indoor unit LEV, LEV2

Refer to the following page(s). [8-8 Troubleshooting LEV

Problems](page 258)

Confirm that the refrigerant service valve is fully open.

Check the fan on the outdoor unit.

Refer to the following page(s). [8-7 Troubleshooting Outdoor

Unit Fan Problems](page 257)

Perform a cooling or heating operation and check the opera-

tion.

Refer to the following page(s).

Check the inlet air temperature on the LED monitor.

— 171 —

GB

Mitsubishi Error Code 1102 is an indication of a communication error between the indoor and outdoor units. This error occurs when the signal line from the indoor unit to the outdoor unit has been disconnected, or if there is a malfunction in either one of these components. The best course of action for resolving this issue is to ensure that all electrical connections are secure and free from any damage, then check the status on both units.

It may also be necessary to reset both units by powering them off and then back on again after about 10 minutes. If none of these solutions work, it could be time to call in a technician for further assistance.

Error code 1102 on a Mitsubishi vehicle is an indication that there is a problem with the fuel injector control circuit. This error code can be caused by faulty wiring or connectors, a loose connection in the system, corrosion on the pins of the connector, or an issue with one of the sensors. If you are seeing this code while trying to diagnose your Mitsubishi vehicle’s engine problems, it’s important to take immediate action and have a qualified technician inspect and repair any faults associated with this particular error.

Mitsubishi 0511102

Mitsubishi 0511102 is a direct drive, AC brushless motor with an output of up to 8.4kW and comes equipped with a built-in controller and encoder. It has various features such as low speed torque capability, high accuracy positioning control, and pulse input function amongst others. With its simple maintenance design it is suitable for use in a wide range of applications from food processing equipment to industrial robots.

Mitsubishi Error Code 1102

Credit: www.ebay.com

What is Error Code 1102 in Mitsubishi Vrf?

Error code 1102 in Mitsubishi VRF systems is an indication that the system has detected a short circuit within the compressor. The short circuit could be due to a defective component or wiring, improper installation, or other issues with the electrical connection between components. In order to diagnose and repair this issue, it may be necessary to inspect all of the electrical connections within the unit and test for any faulty parts.

It is also important to check for any loose connections or signs of damage on wires and terminals before attempting any repairs.

What is Error Code 7110 on Mitsubishi Electric Vrf?

Error code 7110 on Mitsubishi Electric VRF is a communication error between the indoor and outdoor units. The most likely cause of this issue is an incorrect wiring configuration which prevents the two units from communicating properly. This could be due to either incorrect connection or improper installation, such as not connecting all wires correctly.

If this error occurs, it is important to identify the source of the problem and correct it before attempting any further troubleshooting steps. Additionally, professional service may be required if a more complex fault cannot be identified or resolved through basic troubleshooting techniques.

Why is My Mitsubishi Electric Operation Light Flashing 5 Times?

If your Mitsubishi Electric operation light is flashing five times, it usually means that there is an issue with the air conditioner’s compressor. This could be caused by a number of factors such as a faulty capacitor, low refrigerant levels, or a malfunctioning fan motor. It’s best to call in an HVAC technician to diagnose and repair any issues with the compressor as soon as possible in order to prevent further damage and potential health risks from leaking coolant.

What is Mitsubishi Electric Fault Code 1302?

Mitsubishi Electric Fault Code 1302 is an indication of a problem with the transmission fluid pressure sensor circuit. This code is generated when the voltage in the pressure sensor circuit has dropped below a certain threshold, indicating that there may be an issue with either the wiring or components within the transmission system. The cause of this fault code can range from something minor such as a loose wire or connector to something more serious like a faulty component within the transmission system.

A professional technician should be consulted if this code appears to ensure that any issues are addressed and corrected quickly and safely.

Mitsubishi VRF 1102 Error Code (High Compressor Discharge Temp)

Conclusion

In conclusion, Mitsubishi Error Code 1102 can be a frustrating issue to deal with. Fortunately, there are many potential solutions that may help you fix the problem and get your vehicle up and running again. From checking the connection between the sensor and ECU to replacing the air flow meter itself, these steps should help resolve this particular error code.

If all else fails, contact a professional mechanic for assistance in diagnosing and repairing your Mitsubishi vehicle’s mechanical issues.

{
“@context”: “https://schema.org”,
“@type”: “FAQPage”,
“mainEntity”:[{“@type”: “Question”,

“name”: “What is Error Code 1102 in Mitsubishi Vrf? “,

“acceptedAnswer”: {
“@type”: “Answer”,

“text”: ”

Error code 1102 in Mitsubishi VRF systems is an indication that the system has detected a short circuit within the compressor. The short circuit could be due to a defective component or wiring, improper installation, or other issues with the electrical connection between components. In order to diagnose and repair this issue, it may be necessary to inspect all of the electrical connections within the unit and test for any faulty parts. It is also important to check for any loose connections or signs of damage on wires and terminals before attempting any repairs.”

}
}
,{“@type”: “Question”,

“name”: “What is Error Code 7110 on Mitsubishi Electric Vrf? “,

“acceptedAnswer”: {
“@type”: “Answer”,

“text”: ”

Error code 7110 on Mitsubishi Electric VRF is a communication error between the indoor and outdoor units. The most likely cause of this issue is an incorrect wiring configuration which prevents the two units from communicating properly. This could be due to either incorrect connection or improper installation, such as not connecting all wires correctly. If this error occurs, it is important to identify the source of the problem and correct it before attempting any further troubleshooting steps. Additionally, professional service may be required if a more complex fault cannot be identified or resolved through basic troubleshooting techniques.”

}
}
,{“@type”: “Question”,

“name”: “Why is My Mitsubishi Electric Operation Light Flashing 5 Times? “,

“acceptedAnswer”: {
“@type”: “Answer”,

“text”: ”

If your Mitsubishi Electric operation light is flashing five times, it usually means that there is an issue with the air conditioner’s compressor. This could be caused by a number of factors such as a faulty capacitor, low refrigerant levels, or a malfunctioning fan motor. It’s best to call in an HVAC technician to diagnose and repair any issues with the compressor as soon as possible in order to prevent further damage and potential health risks from leaking coolant.”

}
}
,{“@type”: “Question”,

“name”: “What is Mitsubishi Electric Fault Code 1302? “,

“acceptedAnswer”: {
“@type”: “Answer”,

“text”: ”

Mitsubishi Electric Fault Code 1302 is an indication of a problem with the transmission fluid pressure sensor circuit. This code is generated when the voltage in the pressure sensor circuit has dropped below a certain threshold, indicating that there may be an issue with either the wiring or components within the transmission system. The cause of this fault code can range from something minor such as a loose wire or connector to something more serious like a faulty component within the transmission system. A professional technician should be consulted if this code appears to ensure that any issues are addressed and corrected quickly and safely.”

}
}
]
}

My name is Aris, and I am a certified HVAC technician. I have been working in this field for over 5 years and have a lot of experience with different AC units. I write here to help people solve their Air Conditioning problems and find the best solutions for their needs.

If you are having any issues with your air conditioner or are thinking about buying a new one, be sure to check out my blog!

  1. multi city error code 1102

    hi there lads
    happy new year to all engineers
    i am working on multi city , group of indoors not operating, error code 1102 apeares. shut down power to that comp and wait 20 min then turn it on , on the outdoor board reads 0615 flashing then change to 51 flashing , change to 410 flashing and finally to r-08 flashing then only 1 apears whereas on other units 11 1 1 apears. the indoor local controller shows code 1102 again.

    mitsubishi error code 1102 says discharge temp (above 110 deg c )(th1) 407c th11 410 a possibly short of gas, lev3 problem condensor blocked, condensor fan faulty.
    what next??????


  2. Re: multi city error code 1102

    Tell your employer that you need a training course on this product.

    That’s what I’ve done as these systems are too involved for simple fault finding. You waste too much time and embarrass yourself in front of the customer because you can’t resolve what could be a simple problem.

    Nothing personal here, I just get tee’d off with the idea that because we’ve got a screwdriver and a van we can fix anything in twenty-five minutes. [end rant]

    Brian — Newton Abbot, Devon, UK
    Retired March 2015


  3. Re: multi city error code 1102

    The flashing codes when switch on 3 ph power is normal for all City Multi outdoor units.
    This lasts for 2 or 3 mins while the outdoor unit carries out electronic hand shake with all indoor units.
    If you had ever switched on 3ph power to a City Multi outdoor unit before you would know that this is normal process.

    Next step is to use the engineers mode on the outdoor circuit board to display the TH1 sensor data.

    You do need a service manual & get on a training course otherwise you give the product & our trade a bad name because this is a straight forward fault which an engineer could identify within 1/2 hr on site.


  4. Re: multi city error code 1102

    hi i check the thermister got no resistance.


  5. Re: multi city error code 1102

    In your first post you said «1102» is

    «possibly short of gas, lev3 problem condensor blocked, condensor fan faulty»

    Have you checked any of these.

    A fault like this should be relatively straight forward.

    If it isn’t then you need to get booked in on a City Multi training course as the others say.
    Beleive me it’s worth it

    The difference between genius and stupidity is that genius has its limits.

    Marc


  6. Re: multi city error code 1102

    I’ve just re-read your post, you have no resistance on the discharge sensor?

    If thats the case your sensor is damaged.

    Are you sure that you aren’t getting any resistance on it?

    Have you taken it out of the plug that goes onto the board to get a better reading?

    Sometimes the probes don’t make contact with it fully which would give you a false reading

    The difference between genius and stupidity is that genius has its limits.

    Marc


  7. Re: multi city error code 1102

    thank you everybody espcially marc and techmath



  8. Re: multi city error code 1102

    I thought the thermister had no resistance?

    Have you reset the power to the condensor and then turned back on? Does the outdoor unit run ?.

    You really need the outdoor service manual in order to fault find with these units.
    Whats the model number?

    The difference between genius and stupidity is that genius has its limits.

    Marc


  9. Re: multi city error code 1102

    Perhaps you have one of the larger City Multi units which have 2 compressors.
    The direct on line compressor discharge temp sensor is Th12 & if that is fault / open circuit or reading more than 120 deg C then also 1102 fault.
    The discharge temp sensor for the inverter compressor is TH11 & if that is reading more than 120 deg C or open circuit then also 1102 fault.

    You can check any temperature sensor data by using the SW1 dips & LED display on the outdoor circuit board. This is always the best test for temperature sensors because the circuit board displays the the same data it can see from the resistance from the sensor & it only takes a few seconds to do the SW1 dip setting.
    But to do this you need service manual for the exact model you have on site.


  10. Re: multi city error code 1102

    the following is the outdoor details:
    outdoor unit details(o/u)
    model no: PQRY-P200YGM-A
    serial no:78w00034
    comp model no:HNB71FA-YB
    comp serial no :78W24794
    power source(V):
    L1-N 230
    L2-N 230
    L3-N 230
    E-N 0
    indoor model no:PEFY-P20VML-E

    indoor serial no:75W11950

    BC CONTROLLER(MASTER):
    MODEL NO: CMB-P1010V-GA
    SERIAL NO :7YW02896
    any of you near me drop by you will be treated fairly

    Last edited by sork; 02-01-2010 at 11:13 AM.


  11. Re: multi city error code 1102

    Are you sure it is a PQRY and not a PURY?

    If you are then you have a R410A Water Cooled Condensing Unit?

    The difference between genius and stupidity is that genius has its limits.

    Marc


  12. Re: multi city error code 1102

    The discharge sensor is TH4 i think.

    You can get it’s values by checking SW1 on the outdoor board put numbers 1,3,4 + 6 to on…. this will tell you what the discharge sensor is reading.

    Has this system ran whilst you have been with it?

    The difference between genius and stupidity is that genius has its limits.

    Marc


  13. Re: multi city error code 1102

    yes i am sure there are 6 outdoor sharing the DRY AIR condensor NVR 1330 .


  14. Re: multi city error code 1102

    yes it is running with R410A at standing pressure of 150 psig , the other comp (5 of them) have been running no prob , this one i have not seen it running.
    most of indoor coils connected to this outdoor have local remote PAC-SE51CRA, the screen on them goes off(SHADED) immidiatly and the power circle stays each time when i press on/off switch, when i reverse the address no in the G50 controller several second later it goes off.
    the malfunction on G50 shows no error.
    one of the local controller PAR-21MAA goes off immidiatly after i press on/off botton shows the screen standby plus all modes. when i press test botton it shows 1102 and address no of the room.

    Last edited by sork; 02-01-2010 at 12:33 PM.


  15. Re: multi city error code 1102

    On PQRY200YGM-A
    Discharge temp sensor still TH11 as other City Multi units.
    It is on the compressor discharge tube & has completely different ohms reading from all the other sensors at the outdoor unit as it has to read the highest temperature. So it is clear which one it is.

    For 1102 fault & compressor never starting the sensor will be one of the following.
    1/ open circuit
    2/ closed circuit
    3/ reading more than 120 deg C

    If the compressor does run but discharge does run at 120 deg C then there will be some refrigerant flow problem or water flow problem in the system making very low suction pressure which will cause compressor overheat high discharge temp & high discharge SH.

    But I am not going to start giving you the dip settings otherwise you are going to be on here every 5 mins asking for the dip settings for somthing else.
    You need the service manual & then you can read any data you want from the outdoor circuit board.

    The Mitsubishi tech help desk opens at 9am Monday morning.


  16. Re: multi city error code 1102

    The indoor units will not start if 240v power not on.
    Mnet remote controller with address dips.
    In this case the remote controller goes blank after a few seconds but small dot / circle only is displayed.
    This indicate the indoor unit has 30v dc control voltage only.

    If the outdoor unit has 1102 fault it will be displayed at the outdoor circuit board & will be reported at the G50.

    You have a combination of 30v dc Mnet Hotel type remote controllers & 12v dc PAR21 remote controller in the same system.
    This is not normal & not really recommended.

    If the outdoor unit is not displaying 1102 on the display & not showing 1102 fault at the G50 then I suspect the system is ready to run but does not because of power supply problem at indoor units.


  17. Re: multi city error code 1102


  18. Re: multi city error code 1102

    Quote Originally Posted by Thermatech
    View Post

    On PQRY200YGM-A
    Discharge temp sensor still TH11 as other City Multi units.
    It is on the compressor discharge tube & has completely different ohms reading from all the other sensors at the outdoor unit as it has to read the highest temperature. So it is clear which one it is.

    For 1102 fault & compressor never starting the sensor will be one of the following.
    1/ open circuit
    2/ closed circuit
    3/ reading more than 120 deg C

    If the compressor does run but discharge does run at 120 deg C then there will be some refrigerant flow problem or water flow problem in the system making very low suction pressure which will cause compressor overheat high discharge temp & high discharge SH.

    But I am not going to start giving you the dip settings otherwise you are going to be on here every 5 mins asking for the dip settings for somthing else.
    You need the service manual & then you can read any data you want from the outdoor circuit board.

    The Mitsubishi tech help desk opens at 9am Monday morning.

    Whats the difference between YGMA and YHMA? is it just that the latter has been superseeded?

    I was looking at YHMA service manual and it shows the Discharge sensor as TH4 on the refrigerant drawing.

    TH11 in this book is the BC Box LEV control, Liquid inlet temp.

    I’m not questioning you just myself

    The difference between genius and stupidity is that genius has its limits.

    Marc


  19. Re: multi city error code 1102

    Valid point
    discharge temp sensor is TH4 on the very latest City Multi products including water cooled PQRY YHM-A
    I commissioned my first PQRY YHM-A units in November 2009 so I think they have only used up the old stock of YGM-A units reciently.

    The compressor discharge temp sensor was always TH1 on the old R22 systems with one compressor. Then when they started making the larger units with two compressors they called discharge temp sensors inverter comp TH11 & direct on line comp TH12.

    That how it been for about 18 years until now & the current model YHM-A which has discharge temp sensor TH4.

    That why its important to have the correct service manual for the system you are working on.
    If you notice the PQRY YGM-A manual is 235 pages.
    I do not have a photographic memory so I cant recall all the technical info from 235 pages but I do know that I can find most information for trouble shooting in the service manual.


  20. Re: multi city error code 1102

    thank you all we have done it.the prob was not the th11 or other sensors p or t . it was the communication btw indoor bc and the outdoor , the outdoor was unable to shake land with the address no .
    it is not bad idea to do the course , if mr t woudnot explain the thrio power source i would be still at it.
    happy new year to you all


Similar Threads

  1. Replies: 9

    Last Post: 24-01-2010, 06:03 PM

  2. Replies: 3

    Last Post: 09-02-2009, 05:17 PM

  3. Replies: 4

    Last Post: 09-06-2006, 03:31 AM

  4. Replies: 2

    Last Post: 04-07-2005, 05:37 PM

  5. Replies: 1

    Last Post: 30-06-2002, 11:02 AM


Posting Permissions

  • You may not post new threads
  • You may not post replies
  • You may not post attachments
  • You may not edit your posts
  •  
  • BB code is On
  • Smilies are On
  • [IMG] code is On
  • [VIDEO] code is On
  • HTML code is Off

Forum Rules

As an Amazon affiliate, we earn a commision from qualifying purchases.

Mitsubishi City Multi VRF air conditioning systems are famed for their ultra-quiet noise levels, higher savings on installation and running costs, and a significantly reduced footprint.

But much like other air conditioner brands, your mitsubishi city multi air conditioner may, on occasion, malfunction.

Now, a good place to start your troubleshooting when a fault occurs is looking for error codes- and the great thing is that some of the most common mitsubishi city multi error codes can be resolved by performing basic DIY maintenance.

This article lists the most prevalent mitsubishi city multi error codes and their meaning- plus tips to help you fix the problem depending on the exact model you own.

Read through the fault codes- solving the problem causing your air conditioner not to operate properly may be a lot easier than you think:

With many mitsubishi city multi air conditioner models, fault codes are made up of 3 or 4 digits.

Here is a detailed list of mitsubishi city multi error codes, possible meanings, and potential troubleshooting steps (for some):

Mitsubishi City Multi Error Codes- full list

Error code 403 (Mitsubishi City Multi R22, R4O7c, and R410A models)

Meaning: Communication fault between boards

Recommended fix: Check transformer, bus voltage, and inter-connecting cables. Also check inverter error detail for which 2 boards.

Error code 1102 (Mitsubishi City Multi R22, R4O7c, and R410A models)

Meaning: Compressor discharge temperature high (has exceeded 110°C).

Recommended fixes: refrigerant may need to be refilled (could be insufficient). In addition, check discharge thermistor.

Mitsubishi city multi error code 1111, 1112, 1113 (Mitsubishi City Multi R22, R4O7c)

Meaning: Low pressure/temperature problem

Recommended fixes: check thermistors (TH2, TH3, TH4). Also check gas charge, the indoor fan, heat exchanger, and filter

Error code 1202 (Mitsubishi City Multi R22, R4O7c, R410A)

Meaning: Preliminary fault to error code 1102

Error code 1204 (Mitsubishi City Multi R410A)

Meaning: Preliminary heat exchanger gas temperature sensor problem

Recommended fixes: check thermistors 10a & 10b

Error code 1205 (Mitsubishi City Multi R22, R4O7c, R410A)

Meaning: Preliminary thermistor issue(TH5)

Error code 1211 (Mitsubishi City Multi R22, R4O7c)

Meaning: Preliminary thermistor issue(TH2)

Error code 1214 (Mitsubishi City Multi R22, R4O7c, R410A)

Meaning: Preliminary thermistor issue(THHS)

Error code 1216 (Mitsubishi City Multi R22, R4O7c, R410A)

Meaning: Preliminary thermistor issue(TH7)

Error code 1217 (Mitsubishi City Multi R22, R4O7c, R410A)

Meaning: Preliminary thermistor issue(TH8)

Error code 1219 (Mitsubishi City Multi R22, R4O7c)

Meaning: Preliminary thermistor issue(TH9)

Error code 1221 (Mitsubishi City Multi R22, R4O7c, R410A)

Meaning: Preliminary thermistor issue(TH6)

Error code 1243 (Mitsubishi City Multi R4O7c)

Meaning: Preliminary thermistor issue(TH10)

Error code 1301 (Mitsubishi City Multi R4O7c)

Meaning: Low pressure fault(63L operation)-low pressure sensor could be sensing less than 1 bar immediately before starting.

Error code 1302 (Mitsubishi City Multi R22, R4O7c)

Meaning: High pressure issue – check pressure in the system for more than 29 bar(R407c)/38 bar(R410A).

Recommended fixes: Check the high pressure sensor against the gauge pressure

Error code 1368 (Mitsubishi City Multi R22, R4O7c)

Meaning: Pressure sensor issue(PS1) at BC

Recommended fixes: Compare the pressure reading on SW1 (on O/C)

Error code 1370 (Mitsubishi City Multi R22, R4O7c)

Meaning: Pressure sensor fault(PS3) at BC

Recommended fixes: compare the pressure reading on SW1(at O/C)

Error code 1402(Mitsubishi City Multi R410A)

Meaning: Preliminary issue to 1302

Error code 1500 (Mitsubishi City Multi R22, R4O7c, R410A)

Meaning: System overcharge(Abnormal low compressor super-heat ).

Recommended fixes: discharge thermistor TH4

Error code 1501 (Mitsubishi City Multi R22, R4O7c)

Meaning: High compressor shell temperature

Recommended fixes: check for potential shortage of gas.  Can also be due to insufficient indoor index running(comms room units).

Error code 1505 (Mitsubishi City Multi R22, R4O7c)

Meaning: Abnormal suction pressure(generated when low pressure sensor detects a vacuum)

Recommended fixes: check for blockage or a closed valve. Also check for sensor fault

Error code 2500 (Mitsubishi City Multi R22, R4O7c, R410A)

Meaning: there is lack of waterflow on the water circuit

Mitsubishi city multi error code 2502 (R22, R4O7c, R410A)

Meaning: I/C has water level in the drip tray

Troubleshooting steps: check for open/closed circuit(temperature sensors). Also check if the pump is operating correctly.

Error code 2503 (R22, R4O7c, R410A)

Meaning: I/C has water level in the drip tray

Troubleshooting steps: check for closed circuit(on float switch). Also check if the pump is running properly.

Error code 2600 (R22, R410A)

Meaning: Water is leaking from humidifier

Error code 4102 ( R410A)

Meaning: Open phase fault

Troubleshooting steps: Check the power supply as well as noise filter for possible loss of phase. Also check the wiring and fuses.

Error code 4103 (R22, R4O7c, R410A)

Meaning: Reverse phase issue.

Troubleshooting steps: -check phase rotation. Also check if there is loss of phase (through noise filter). Finally check if there is a blown fuse or if the high pressure switch is open (at power on)

Error code 4108 ( R410A)

Meaning: Over current protection (on DOL compressor)

Troubleshooting steps: Check the following parts: power supply, contactor, and compressor

Error code 4115 (R22, R4O7c, R410A)

Meaning: power supply abnormal

Troubleshooting steps: – check power, connections, fuses, and PCB

Error code 4116 (R22, R4O7c, R410A)

Meaning: Fan motor abnormal

Troubleshooting steps: check fan motor as well as the board (relates to the indoor unit/Lossnay unit)

Error code 4210 ( R22)

Meaning: Compressor over current fault

Troubleshooting steps: check the inverter balance. Also check the compressor and inverter.

Error code 4220 (R4O7c, R410A)

Meaning: Low BUS voltage on inverter board (Less than 289VdcDC detected).-

Troubleshooting steps: check mains supply

Error code 4225 (R410A)

Meaning: Low DC voltage detected on Vdc on the fan inverter

Troubleshooting steps: check the CNVdc for 300Vdc (on diode stack). Also check power supply(mains) to your outdoor unit

Error code 4230 (R22, R4O7c, R410A)

Meaning: High temp on heat sink (on inverter)

Troubleshooting steps: check for blockages (in air duct). Also check if the INV fan has failed. Finally test if the thermistor has failed.

Error code 4235 (R410A)

Meaning: Fan inverter heat sink overheating protection due to reduced airflow through the heat sink or a fan motor fault. This could also indicate THHS thermistor issue.

Error code 4240 (R22, R4O7c, R410A)

Meaning: Over current protection- high current may have been detected for 10 (or more) minutes.

Possible fixes: check inverter balance. Also try to identify what may be causing reduced airflow through the heat sink

Error code 4245 (R410A)

Meaning: Over current protection due to potential ACCT current sensor problem (Should read 280ohms between pins 1 and 2 and across the pins 3 and 4.

Error code 4250 (R410A)

Meaning: Over current protection (may be caused by Inverter IPM fault/Compressor lock)

Troubleshooting steps:  check inverter balance

Error code 4255 (R410A)

Meaning: Inverter cooling fan issue.

Troubleshooting steps:  if using high static fan, you should check that the SW3-9 is on.

Error code 4260 (R4O7c, R410A)

Meaning: Preliminary overheat protection (on inverter heat sink) probably caused by reduced airflow through the heat sink. The issue can also be due to a fan motor problem or THHS thermistor fault.

Error code 5101, 5102, 5103, 5104 (R22, R4O7c, R410A)

Meaning:Thermistor fault (at indoor/outdoor unit)

Troubleshooting steps:  check error code address

Error code 5105 (R22, R4O7c, R410A)

Meaning:TH5 open/short circuit

Troubleshooting steps:  The TH may be disconnected from the board. Check.

Error code 5106 (R22, R4O7c, R410A)

Meaning:TH6 open/short circuit

Troubleshooting steps:  The TH may be disconnected from the board. Check.

Error code 5107 (R22, R4O7c, R410A)

Meaning:TH7 open/short circuit

Troubleshooting steps:  The TH may be disconnected from the board. Check.

Error code 5108 (R22, R4O7c)

Meaning:TH8 open/short circuit

Troubleshooting steps:  The TH may be disconnected from the board. Check.

Error code 5109 (R4O7c)

Meaning:TH9 open/short circuit

Troubleshooting steps:  The TH may be disconnected from the board. Check.

Error code 5110 (R22, R4O7c, R410A)

Meaning:TH10 open/short circuit

Troubleshooting steps:  The TH may be disconnected from the board. Check.

Error code 5111 (R22, R410A)

Meaning: BC box thermistor fault (due to TH11 open/short circuit or disconnection from board/pipe)

Error code 5112 (R22, R4O7c, R410A)

Meaning: BC box thermistor fault (due to TH10 open/short circuit or disconnection from board/pipe)

Error code 5113 (R22), Error code 5114 (R22)

Meaning: BC box thermistor fault (due to TH open/short circuit or disconnection from board/pipe)

Error code 5115 (R22, R410A)

Meaning: BC box thermistor fault (due to TH15 open/short circuit or disconnection from board/pipe)

Error code 5116 (R22, R410A)

Meaning: BC box thermistor fault (due to TH16 open/short circuit or disconnection from board/pipe)

Error code 5201 (R22, R4O7c, R410A)

Meaning: Pressure sensor problem (outdoor unit or BC box)

Troubleshooting steps:  check error code address or SW 1 pressure sensor readings.

Error code 5202 (R22)

Meaning: Pressure sensor problem (PS2) in BC box

Error code 5203 (R22, R4O7c, R410A)

Meaning: Pressure sensor problem (outdoor unit or BC box)

Troubleshooting steps:  check error code address or SW 1 pressure sensor readings.

Error code 5301 (R4O7c, R410A)

Meaning: Current sensor fault (or  ACCT/DCCT)

Troubleshooting steps:  check inverter error details

Error code 5401 (R410A)

Meaning:Temperature sensor fault

Troubleshooting steps:  check CN 30 for humidity sensor

Error code 5701 (R410A)

Meaning: float switch connector loose

Troubleshooting steps:  check switch. Also check CN4F (on the indoor unit)

Error code 6201 (R410A)

Meaning: TB7 transmission line has communication error

Troubleshooting steps:  check for abnormality in voltage/short

Error code 6202 (R410A)

Meaning: Transmission processor hardware fault

Troubleshooting steps:  check for short/noise on M-Net cable

Error code 6600 (R22, R4O7c, R410A)

Meaning: Repeat address issue -it means the same address has been assigned two (or more units)

Troubleshooting steps:  the repeated address need to be corrected

Error code 6601 (R410A)

Meaning: Polarity setting fault (there is no voltage –or there is a short circuit -on m-net transmission line)

Error code 6602 (R22, R4O7c, R410A)

Meaning: Hardware error on transmission processor. It may also indicate noise interference or even a polarity problem on TB 7.

Error code 6603 (R22, R4O7c, R410A)

Meaning: Bus circuit busy.

Troubleshooting steps:   check if the  indoor unit (or anything else) is wired into TB7 (instead of TB3) and correct the wiring error

Mitsubishi city multi error code 6607 /mitsubishi vrf error code 6607 (R22, R4O7c, R410A)

Meaning: Communication issue (no response is coming from unit whilst the system is operational)

Error code 6608 (R22, R4O7c, R410A)

Meaning: Communication error -there is loss of voltage (or noise) entering into the transmission line

Error code 6831 (R410A)

Meaning:MA R/C communication fault

Troubleshooting steps:   check connections on TB 15. You can also check  that the controller had been removed while the I /C was powered

Error code 6832, 6833, 6834 (R410A)

Meaning:MA controller communication fault

Troubleshooting steps:   check cable length – should not be bigger than 500m. Also, check for proper connection and that the proper type of cable has been used.

Error code 7100 (R22, R4O7c, R410A)

Meaning: Over capacity

Error code 7101 (R22, R4O7c, R410A)

Meaning: Capacity setting issue – SW2 set wrong (on indoors), SW5 set wrong on YHMA outdoor (SW3-10 on older kits)

Mitsubishi city multi error code 7102 (R22, R4O7c, R410A)

Meaning: It may point to an error in the number of units you have  connected or indicate loss of MNet voltage (short/break). It may also mean there is no power to the BC or even wrong SW 5 setting on box (or even wrong box type).

Error code 7105 (R22, R4O7c, R410A)

Meaning: Address setting issue – OC/BC addressed incorrectly

Error code 7106 (R4O7c, R410A)

Meaning: Attribute setting fault (SW3-1 setting on GUF)

Error code 7107 (R4O7c, R410A)

Meaning: Port setting issue- check if there  is too much capacity on one port. Also check  wiring, SW2 setting, SW14 setting (it could be wrong too) or even for wrong units (on a box if using multiple boxes)

Wrap up

This ‘mitsubishi city multi error codes check list’ provides an easy-to-use reference guide on all mitsubishi city multi error codes across the company’s product range.

More troubleshooting ideas and guidance can be found on the trouble-shooting section of your specific model’s service manual.

Be sure to contact a qualified HVAC technician if your aircon need advanced repair(s).

RELATED:

LG mini split error codes and troubleshooting guide 

Trane thermostat error codes – comprehensive

Поддержание оптимальной температуры в комнате необходимо для комфортных условий. Когда
кондиционер ломается, жаркая погода может испортить весь день, потому что заставит
чувствовать себя неприятно. Следует определить код ошибки кондиционеров и провести
дальнейшую диагностику, чтобы вернуть устройство к работе.

Как определяются коды ошибки кондиционеров Mitsubishi Electric

Для того чтобы считать коды ошибок кондиционеров Mitsubishi Electric, воспользуйтесь
инструкцией производителя, а затем расшифруйте код при помощи таблицы:

P1  Неисправность датчика температуры ТН3 
Р2  Неисправность датчика, считывающего данные TH5-теплообменника 
Р4  Дренажный поддон наполнен выше нормы (также возможна неисправность датчика-поплавка CN4F) 
Р5  Неисправность помпы, установленной в дренажном отсеке 
Р6  Неправильное выполнение команды понижения или повышения температуры 
Р8  Неправильная температура установилась в теплообменнике 
Р9  Неисправность датчика, считывающего данные ТН2-теплообменника 
РА  Компрессор был аварийно и принудительно остановлен 
Е0  Невозможна передача сигнала к пульту управления 
Е1  Кнопки на пульте управления неисправны 
Е2  Адреса внутренних систем дублированы 
Е3  Адрес наружного блока указан неправильно 
Е4; Е5  Приемник сигнала с пульта управления неисправен 
Е6  Есть замыкание в соединении внутреннего и внешнего блока 
Е7  Ошибка передачи данных в системе 
Е8  Обрыв цепи около датчика приема данных 
Е9  Не получается связаться с передатчиком 
Е0  Низкий заряд батареи пульта 
ЕА  Неправильная установка электросети и соединений проводов 
ЕВ  Защита электросети от перенапряжения 
ЕС  Не получилось запустить работу системы по таймеру 
Ed  Необходимо сбросить все до базовых настроек 
ЕЕ  Невозможно передать данные на передатчик 
EF  M-NET ошибка – неправильное соединение проводов 
U1  Датчик 63Н указывает на давление выше нормы (либо температуру выше нормы) 
U1  Фатальная ошибка 
U2  Датчик 49С говорит о низком давлении при заборе воздуха или низком уровне хладагента 
U2  Компрессор работает на высокой температуре 
U3  Варистор конденсатора неисправен 
U4  В электросети датчика температуры внешнего блока есть обрыв или короткое замыкание 
U5  Датчик температуры конденсатора сигнализирует о превышении нормы 
U6  Обнаружена токовая перегрузка электросети компрессора, устройство остановлено 
U7  Датчик 49С указывает на ошибку 
U8  Принудительная остановка моторчика вентилятора, установленного во внешнем блоке 
U9; UH  Отклонение от нормы напряжения электрического тока, поступающего от сети, ошибка в показаниях датчика напряжения тока 
UA  Ошибка пускового реле компрессора 
UD  Компрессор перегрелся 
UL  Низкое давление хладагента 
UF  Слишком высокий уровень напряжения, остановка компрессора 
UP  Перегрузка электросети, принудительная остановка компрессора 
Fb  Ошибка системы программирования 
F1  Нет данных от датчика температуры ТН3 
F2  Обрыв фазы на участке L3 
F3  Неправильное соединение с внутренней платой управления – нет сигнала 
F4  Разомкнулся разъем 
F7  Нарушена последовательность в фазах шлейфа 
F8  Нестабильное напряжение сети 
F9  Нет сигнала в разъемах 
FA  Обрыв фазы на участках L2 

Ошибки кондиционеров Mitsubishi Electric на пульте ДУ 

Е0  Не получается передать команду на кондиционер 
Р1  Данные о всасываемом воздухе считываются неправильно 
Р2  Неисправность трубочек 
Р3  Системная ошибка 
Р4  Нет данных от датчика Drain 
Р5  Утечка переполнения защиты механизма 
Р6  Неправильно проведено снижение или увеличение температуры 
Р7  Системная ошибка (формирование данных) 
Р8  Обрыв соединения 

LED лампы

Статус операции Проверка выдачи кода ошибки 
LD1  Компрессор 
LD2  Регулировка температуры 
LD3  Проведение операции 63Н3 
LD4  Компрессор работает во время операции 63Н2 
LD5  Включен вентилятор 
LD6  Работает четырехходовой клапан 
LD7  Перепускной клапан 
LD8  Работает нагреватель картера 
Индикация светодиода   
Вспышка раз в 2 секунды  Неисправно питание конвертора, внешнее питание, термистор или система управления наружного блока 
Две вспышки раз в 2 секунды  Защита от короткого замыкания 
Три вспышки раз в 2 секунды  Защита от превышения нормальной температуры системы нагнетания 
Четыре вспышки раз в 2 секунды  Защита от превышения нормальной температуры термистора 
Пять вспышек раз в 2 секунды  Защита от превышения нормы давления в системе 
Семь вспышек раз в 2 секунды  Защита от случайного старта системы 
Восемь вспышек раз в 2 секунды  Защита ошибки в установке температуры 
Одна вспышка  Снизилось напряжение в электросети 
Три вспышки  Сработал режим размораживания 
Четыре вспышки  Высокая температура системы нагнетания 
Пять вспышек  Термистор наружный 
Семь вспышек  Низкая температура системы нагнетания 
Восемь вспышек  Конвертор защищается 
Девять вспышек  Инвертор проверяется 