Cyberpower cps600e коды ошибок

CPS600E

1.

Overheat Protection: The EPS output will be interrupted. After 30 seconds, the machine shuts

down and the LCD display output voltage is zero.

Over-Load Protection: : : : The EPS output will be interrupted. After 30 seconds, the machine shuts

2.

down and Over Load Icon lights on the LCD display.

Battery Missing: : : : You should hear a long beep and Battery Indicator flashes。

3.

4.

Low Battery Protection: The EPS output will be interrupted. After 30 seconds, the machine shuts

down and the LCD display output voltage is zero.

5.

The following table shows each corresponding warning message on the LCD display and the alarm

reacts during the machine shut down:

LCD

Warning

Display

Over Load Icon

Zero Output

Voltage

Can Not Start Up

Copyright © 2010 CyberPower Systems, Inc.

Alarm

Over Load Output-Off — Load

Constant tone

exceed the rating of EPS.

High Temperature Output-Off

Low Battery Output-Off

— Insufficient battery capacity.

Over Charge or AVR Error—

Constant tone

In Line Mode, battery is

overcharged or AVR is faulty.

Short Output-Off — Output

Short Circuit Protection

Line

Output-Off — incorrect Input/

Output connection

None

Cold

Voltage

battery voltage is too high

during cold start.

Condition

Input/

Output

Error

Start

Battery

High

Output-Off

the

Solution

Check

total

load

to

confirm the rating of

EPS.

Check fans function and

air vent clearances.

Recharge the battery.

Inform service agents.

Check the EPS output

to see if there is a short

circuit.

Check

Input/

Output

connection.

Check the reason for

battery over-voltage.

10

CyberPower CPS600E User Manual

  • Contents

  • Table of Contents

  • Troubleshooting

  • Bookmarks

Quick Links

User’s Manual

CPS600E

CyberPower Europe

CyberPower Systems B.V.

Flight Forum 3545, 5657DW Eindhoven, The Netherlands

Tel: +31 (0)40 2348170

Fax: +31 (0)40 2340314

Website: http://eu.cyberpowersystems.com/

E-mail: sales@cyberpower-eu.com

K01-0000186-00

loading

Related Manuals for CyberPower CPS600E

Summary of Contents for CyberPower CPS600E

  • Page 1
    User’s Manual CPS600E CyberPower Europe CyberPower Systems B.V. Flight Forum 3545, 5657DW Eindhoven, The Netherlands Tel: +31 (0)40 2348170 Fax: +31 (0)40 2340314 Website: http://eu.cyberpowersystems.com/ E-mail: sales@cyberpower-eu.com K01-0000186-00…
  • Page 2: Table Of Contents

    DEFINITIONS FOR ILLUMINATED LCD ……7 EPS STATUS INQUIRY AND FUNCTIONS SETUP ….. 8 GENERAL MODE …………….. 8 SET-UP MODE ………………8 FAULT WARNING DISPLAY AND ALARM ……10 TROUBLESHOOTING …………11 TECHNICAL SPECIFICATIONS ……… 12 Copyright © 2010 CyberPower Systems, Inc.

  • Page 3: Safety And Emc Instructions

    Condensation from the aquarium can cause the unit to short out. DO NOT INSTALL THE EPS WHERE IT WOULD BE EXPOSED TO DIRECT SUNLIGHT OR NEAR HEAT! DO NOT BLOCK OFF VENTILATION OPENINGS IN THE EPS’S HOUSING! Copyright © 2010 CyberPower Systems, Inc.

  • Page 4
    CPS600E SAFETY: EN62040-1-1 EMI: Conducted Emission: IEC/EN 62040-2…Category C2 Radiated Emission: IEC/EN 62040-2……Category C2 Harmonic Current: IEC/EN61000-3-2 Voltage Fluctuations and Flicker: IEC/EN61000-3-3 EMS: IEC/EN61000-4-2(ESD) IEC/EN61000-4-3(RS) IEC/EN61000-4-4(EFT) IEC/EN61000-4-5(lightning surge) IEC/EN61000-2-2 (Immunity to low frequency signals) Copyright © 2010 CyberPower Systems, Inc.
  • Page 5: Installing Your Eps

    EPS off and unplug the equipment from the AC outlet. Ensure that the equipment plugged into the outlet does not exceed the UPS unit’s rated capacity (600VA/420W for CPS600E). If the rated capacities of the unit are exceeded, an overload condition may occur and cause the UPS unit to shut down or the input fuse to blow.

  • Page 6: Basic Operation

    Connect red (positive (+)) battery cable to the red (positive (+)) connector on the external battery. Note: The Battery cable is 10AWG / 4 feet. 9. DC Fuse The fuse provides optimal overload protection for battery mode operation. Copyright © 2010 CyberPower Systems, Inc.

  • Page 7: Replacing The Battery

    Do not lay tools or metal parts on top of battery or any terminals. Wear rubber gloves and boots. Determine if the external battery is inadvertently grounded. If grounded, remove the source of ground. CONTACT WITH GROUNDED BATTERY CAN RESULT IN ELECTRICAL SHOCK! Copyright © 2010 CyberPower Systems, Inc.

  • Page 8: Definitions For Illuminated Lcd

    EPS outlets until the icon disappears and the alarm stops being activated. 7. LOAD CAPACITY: Load CAPACITY is also shown on the bar chart; equal 25% load capacity for each segment. 8. BATTERY VOLTAGE: BATT. VOLTAGE indicates the voltage of battery. Copyright © 2010 CyberPower Systems, Inc.

  • Page 9: Eps Status Inquiry And Functions Setup

    EPS will be used. 220V and 230V may be selected. The system default setting is 220V. Function description: AVR Dynamic Voltage Compensation works automatically based on the system voltage settings. Static Frequency Tolerance: There are 6 settings (1,2,4,6,8,10%), and the default setting is +/-10%. Copyright © 2010 CyberPower Systems, Inc.

  • Page 10
    Note: If user wants to return to general mode without saving changes, there are two methods: 1. Wait for the backlight to turn off 2. Press and hold the “Display” toggle for 10 seconds Copyright © 2010 CyberPower Systems, Inc.
  • Page 11: Fault Warning Display And Alarm

    Input/ Output Output-Off — incorrect Input/ connection. Output connection Can Not Start Up None Cold Start Battery High Voltage Output-Off Check the reason for battery voltage is too high battery over-voltage. during cold start. Copyright © 2010 CyberPower Systems, Inc.

  • Page 12: Troubleshooting

    220/230V outlet. The EPS will not turn on. Contact CyberPower Systems about The battery is worn out. replacement batteries at service@cyberpower-eu.com Contact CyberPower Systems via Mechanical problem. phone or visit our website at eu.cyberpowersystems.com Copyright © 2010 CyberPower Systems, Inc.

  • Page 13: Technical Specifications

    Environmental Operating Temperature 32°F to 104°F ( 0°C to 40°C ) Operating Relative Humidity 0 to 90% Non-Condensing Physical Dimensions (L*W*H)( mm ) 240 * 162 * 90 Weight (Kg) Agency Certificated CE, SONCAP Copyright © 2010 CyberPower Systems, Inc.

  • Page 14
    CPS600E Copyright © 2010 CyberPower Systems, Inc.
  • Page 15
    CPS600E Copyright © 2010 CyberPower Systems, Inc.
  • Page 16
    Flight Forum 3545, 5657DW Eindhoven, The Netherlands Tel: +31 (0)40 2348170 Fax: +31 (0)40 2340314 Website: http://eu.cyberpowersystems.com/ E-mail: sales@cyberpower-eu.com Entire contents copyright © 2010 CyberPower Systems, Inc. All rights reserved. Reproduction in whole or in part without permission is prohibited. Copyright © 2010 CyberPower Systems, Inc.

File Specifications:

2292/2292459-cps600ein.pdf file (16 Jun 2023)

Accompanying Data:

CyberPower CPS600E-IN UPS PDF Operation & User’s Manual (Updated: Friday 16th of June 2023 09:58:10 PM)

Rating: 4.1 (rated by 74 users)

Compatible devices: OR1500LCDRTXL2U, CP825AVRLCD-G Series, CP1350EAVRLCD, SMP1400EILCD, Value1200ELCD, OLS3S15KE, SL750U-FC, PR750ELCD.

Recommended Documentation:

Operation & User’s Manual (Text Version):

(Ocr-Read Summary of Contents of some pages of the CyberPower CPS600E-IN Document (Main Content), UPD: 16 June 2023)

  • 2, 2 SAFETY AND EMC INSTRUCTIONS This manual contains important safety instructions. Please read and follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install, or operate your Emergency Power System (EPS). CAUTION! To prevent the risk of fire or electric shock, install in a temperature and humidity control…

  • 3, 3 EMS: IEC/EN61000-4-2(ESD) IEC/EN61000-4-3(RS) IEC/EN61000-4-4(EFT) IEC/EN61000-4-5(lightning surge) IEC/EN61000-2-2 (Immunity to low frequency signals) INSTALLING YOUR EPS UNPACKING Inspect the EPS upon receipt. The box should contain the following: (1) EPS Unit x 1; (2) User Manual x 1; (3) Input Power Cord x 1; (4) DC Fuse x 2 AUTOMATIC VOLTAGE REGULATOR Utility power is inconsistent. The EPS increases low voltage to comp…

  • 4, CyberPower CPS600E-IN 4 BASIC OPERATION DESCRIPTION 1. Power Switch Used as the master on/off switch for equipment connected to the AC outlet. 2. Power On Indicator This LED is above the power switch. It illuminates when the utility condition is normal and the AC outlet is providing power, free of surges and spikes. 3. Multifunction LCD Readout High resolution and intelligent LCD display shows all the EPS information with icons and mes…

  • 5, 5 REPLACING THE BATTERY CAUTION! Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the battery. Battery service should only be done by qualified professionals. CAUTION! Use only the specified type and number of external batteries. Please see the technical specifications for replacement batteries. CAUTION! The battery may present a risk of electrical shock. Do not dispose of battery in a fire as it ma…

  • 6, 6 5. SILENT MODE Icon: This icon appearing indicates that the buzzer does not beep in the silent mode until the low battery capacity. 6. OVER LOAD Icon: This icon appearing and an alarm activated indicate that the overload condition. To relieve the overload, unplug your equipment from the EPS outlets until the icon disappears and the alarm stops being activated. 7. LOAD CAPACITY: Load CAPACITY is also show…

  • 7, 7 d. Static Frequency Tolerance: There are 6 settings (1,2,4,6,8,10%), and the default setting is +/-6%. Function description: The settings may be adjusted to the quality of the electricity in use. e. Slew Rate: Also called Dynamic Frequency Tolerance. There are 5 different settings (0.25,0.5,1,2,4 Hz/Sec). The default value is 4Hz/sec. Function description: “Slew Rate” indicates the tolerance of a device in accepting frequency variances. The lower “Slew Rate” results in l…

  • 8, 8 4. Low Battery Protection: The EPS output will be interrupted. After 30 seconds, the machine shuts down and the LCD display output voltage is zero. 5. The following table shows each corresponding warning message on the LCD display and the alarm reacts during the machine shut down : LCD Warning Display Alarm Condition Solution Over Load Icon Constant tone Over Load Output-Off — Load exceed the rating of EPS. Check total load to confirm the rating of EPS. Zero Ou…

  • 9, 9 TROUBLESHOOTING Problem Possible Cause Solution Outlet does not provide power to equipment. Input fuse is blown due to overload. Turn the EPS off and unplug the connected equipment. Unplug the power cord of the EPS then remove the fuse compartment beneath the AC inlet of the EPS and replace the blown fuse with a spare one. Lock the compartment back to the EPS. Connect power cord then turn the EPS on. Make sure that your spare fuse meets the specification and the equip…

  • 10, 10 TECHNICAL SPECIFICATIONS Model CPS600E-IN Capacity (VA) 600VA Capacity (Watts) 420W Operation Technology AVR ( Single Boost & Single Buck ) AC Input Input Voltage Range 170Vac – 270Vac Input Frequency Range 50 / 60 Hz +/- 5Hz AC Output Number of Phase Single Phase On Battery Typical Output Voltage 0 ~40% LOAD Pure Sine Wave at 230Vac +/- 5 % 40~100% LOAD Trapezoidal Wave at 230Vac…

  • CyberPower CPS600E-IN User Manual

  • CyberPower CPS600E-IN User Guide

  • CyberPower CPS600E-IN PDF Manual

  • CyberPower CPS600E-IN Owner’s Manuals

Recommended: PN50B850Y1FXZA, DM/ICEVC-BH39, housEvolve, 160-LED, THE ECONOMIZER 153.333315 HA

Links & Tools

Operating Impressions, Questions and Answers:

Понравилась статья? Поделить с друзьями:
  • Cummins ошибка 434
  • Cvt kawasaki ошибка kawasaki
  • Cxuiuexe exe ошибка приложения
  • Cxmldsign ошибка исполнения функции 1627
  • Cummins ошибка 2271