Hi fellow spicers,

We have a mixture of APC SMART UPS that have been in storage for about 1-2 years.

Disconnected the isolator plug on the back before they were packed away.

We have just got out 3 of them, all APC 1500 SMART UPS and they are all showing «Warning State: Connect Battery».

One of these units sorted themselves out after leaving it overnight. The other two are still beeping and showing the message.

We put a volt meter on the batterys and they are holding charge. Also checked the internal battery connector for any corrosion or loose connections.

Another thing which is strange is that as soon as you pull the plug from it, the UPS stays running which would show that the battery’s are working.

Installed date for the battery’s are 2011 but they have only had about 6 weeks use before being left plugged in and eventually packed away. 

Anybody got any ideas on whats going on with them and how to fix them?

We have a few of the bigger APC units which might have the same problem.

Asked

Viewed
45k times

I have an APC Smart-UPS X 1500V which I just connected to a power source. When I turned the device on it was beeping and giving a flashy red light at the most right icon of the control panel.

enter image description here

The error message «Warning State: Connect Battery» was displaying on the screen of the control panel.

I tried resetting the device to factory defaults.

What is causing this and how can I fix this issue?

asked Jul 7, 2015 at 11:45

Bas's user avatar

BasBas

2653 gold badges9 silver badges21 bronze badges

16

You must log in to answer this question.

Browse other questions tagged

.

Brand Logo

Important Announcement: Protecting our Community from Spam Events

Dear Members, we apologize for any disruption or inconvenience caused by the
recent spam incidents, and we want to assure you that our dedicated team is
actively investigating each reported instance of spam and implementing robust
measures to mitigate the impact. Learn more on
Spams Mitigation Guidelines

Thank you,

Schneider Electric Community Team

APC UPS Data Center & Enterprise Solutions Forum

Schneider, APC support forum to share knowledge about installation and configuration for Data Center and Business Power UPSs, Accessories, Software, Services.

Options

  • Subscribe to RSS Feed
  • Mark Topic as New
  • Mark Topic as Read
  • Float this Topic for Current User
  • Bookmark
  • Subscribe
  • Mute
  • Printer Friendly Page


Invite a Co-worker

Send a co-worker an invite to the portal.Just enter their email address and we’ll connect them to register. After joining, they will belong to the same company.

Send Invite Cancel

Invite a Colleague

Found this content useful? Share it with a Colleague!

Replies 0

SMART-UPS 2200 — Warning State: Connect Battery. If anything else besides the battery is bad then it would be easier to buy a new UPS. In the example above the unit was manufactured in the year 2002 duringthe 49th week. Warning State: Connect battery Load: 55% Batt: 100% Today, I could smell a sort of sulfur/sulphur/rotten egg smell when I . I’m excited to be here, and hope to be able to contribute. I tested a SMT1000 here and the charger was putting out 27.6v DC so if your system is close to that the charger should be good. The instructions do not indicate anything additional required to get the unit operational. What is causing this and how can I fix this issue? Slide out the old APC RBC6 battery pack and disconnect the black and red power cables. Site design / logo 2023 Stack Exchange Inc; user contributions licensed under CC BY-SA. Get answers you need by browsing topic-related Frequently Asked Questions (FAQ). Yellow indicates a Warning state. There is very high, very low, or distorted input line voltage. You should inspect for any corrosion, but the UPS is probably okay. Please invite another co-worker. If the battery is near the end of its service life, consider replacing the battery even if the replace battery indicator is not yet illuminated. When I turned the device on it was beeping and giving a flashy red light at the most right icon of the control panel. We put a volt meter on the batterys and they are holding charge. It may be configured as the ‘group manager’ of the two (especially if the units share sensor data). It might make sense to contact your local tech support while you are with the unit for further assistance. After a power failure about 1 month ago, 1 unit (Mdl: SMT2200 / SN: JS1009016871) started beeping about 5 minutes after power restored. Afrikaans; ; Asturianu; Bn-lm-g; Catal; Cebuano; etina; Dansk; Deutsch; Espaol; Esperanto; Euskara; ; Franais; /Hak . Create your free account or log in to subscribe to the forum — and gain access to more than 10,000+ support articles along with insights from experts and peers. Thanks @bqDraco. Powered down equipment connected to UPS, powered down UPS, then disconnected and reconnected the battery. Take a picture of it and post it. I have an APC Smart-UPS X 1500V which I just connected to a power source. — the incident has nothing to do with me; can I use this this way? Configuring power outage shutdown via APC UPS’s. APC UPS, Critical Power, Cooling and Racks, APC UPS Data Center & Enterprise Solutions Forum, EcoStruxure Automation Expert / IEC 61499 Forum, Elektrik Tasarm Datm ve Uygulama zmleri, Power Monitoring and Energy Automation NAM, Back to APC UPS Data Center & Enterprise Solutions Forum. Power failure lasted several hours; connected equipment was powered down and UPS powered down . LCD panel showed battery at 85%; Self-Test ran and passed. after being in storage. Monday-Friday between 8am 8pm EST. APC’s forum quotes «The battery constants give the battery status via their life expectancy. Is there a single-word adjective for «having exceptionally strong moral principles»? Am I missing something, or do I have a problem with this unit? @ChrisPowell No, I didn’t just buy it, we had it in use for the company and it got replaced, now when i’m trying to start it back up, i get this error. Replace Battery: The battery is nearing the end of its useful life. The replacement battery is not properly connected. Maximize the lifespan of your UPS, and protect your investment, with pro-active notifications for firmware upgrade, device maintenance and warranty protection. I can’t give you specifics on exactly how APC units will respond with alarms, etc. Pull the battery out half way. At that point, you may need to hire a hazmat cleanup service to remove the battery and clean up the area. — Disconnected battery notification Warns when a battery is not available to provide backup power. Stack Exchange network consists of 181 Q&A communities including Stack Overflow, the largest, most trusted online community for developers to learn, share their knowledge, and build their careers. This co-worker has already been invited to the Exchange portal. A week ago I got the following error on my APC Smart-UPS 1000 which I muted. Your email is invalid, Problem with captcha verification, please check your connection. Published on: 12/13/2017 Last Modified on: 9/30/2021. 2023-01-20 Stack Exchange network consists of 181 Q&A communities including Stack Overflow, the largest, most trusted online community for developers to learn, share their knowledge, and build their careers. Learn More. Blue indicates an Informational state . 20 ppm is the acceptable ceiling concentration established by OSHA. Next morning when I checked, front LCD display was asking if new battery was installed. The UPS front panel display illuminates. None. This was originally posted on APC forums on 2/3/2020. Why is there a voltage on my HDMI and coaxial cables? Upon power up, all was good. The battery connector plug is not securely connected. 800 ppm is the lethal concentration for 50% of humans for 5 minutes exposure (LC50). I bet the batteries are End Of Life and they were last replaced 7 years ago. I tried resetting the device to factory defaults. This co-worker has already been invited to the Exchange portal. If your Fiber equipment is plugged into the Battery Backup outlets, your Fiber Jack, Network Box, and Phone Box should continue to work until battery power is depleted. Buy APC Back-UPS Connect Lithium Ion UPS with Mobile Power Pack, USB Charging Ports for Echo and Network Routers (BGE50ML) (Not sold in Vermont) at Amazon. Indoor Humidity 52% (Ideal Humidity) Dew Point 50 F. Air Quality Fair. Share it with a Colleague! If the light is very dim, check the utility voltage. Site design / logo 2023 Stack Exchange Inc; user contributions licensed under CC BY-SA. Power failure lasted several hours; connected equipment was powered down and UPS powered down when battery level reached approximately 40%. What video game is Charlie playing in Poker Face S01E07? By clicking Accept all cookies, you agree Stack Exchange can store cookies on your device and disclose information in accordance with our Cookie Policy. We have 6 identical SMART-UPS 2200 units purchased about 6 months ago. Please note that the LCD screen may be lit even though the UPS is OFF. Just looked at the manual for that UPS. This video shows how to replace the battery in a APC Smart UPS 750. Perhaps a cleaning of any affected surfaces with a solution of baking soda and water to neutralize the acid? For more information on SmartConnect plan options and how to get started, click here. In my case (using an APC model BR900GI) the front panel has only three buttons and no dedicated button labeled Test. Tlchargements de la version dvaluation, Cookies, Publicits et courriers lectroniques, Passer des commandes rapidement et facilement, Afficher les commandes et suivre ltat de votre expdition, Crez et accdez une liste de vos produits. With these systems, your devices can be turned off properly when a power outage occurs, preventing harmful system crashes from occurring. I replaced the battery and there is no change. When starting the reset process, you must first disconnect any device placing a load on the UPS. Cloud Cover 92%. Disconnected the isolator plug on the back before they were packed away. 2021-06-28 Be sure that all battery connections are secure. Be sure that the power cable is securely connected to the unit and to the utility power supply. Difficulties with estimation of epsilon-delta limit proof. During the last power outage, about a month ago, which lasted about 5 hours, when the battery had dropped to about 40%, and still no ETA when power would be restored, I powered down connected equipment; then turned off the UPS. That’s a smell you can’t escape from. APC smart UPS 1000 how to open front metal cover. You would want to make sure the battery is good and that everything is firmly connected. Find your genuine APC replacement battery here: https://www.apc.com/shop/us/en/tools/replacement-battery-selectorTo learn more, please visit the APC by Schneider Electric FAQ:http://www.apc.com/us/en/faqs/FA156584/Click here to subscribe to Schneider Electric: https://www.youtube.com/c/schneiderelectric?sub_confirmation=1Connect with Schneider Electric:Global Website: http://spr.ly/SchneiderElectricDiscover our Services: http://spr.ly/SE-ServicesVisit our Blog: http://spr.ly/SE-BlogGain Insights: http://spr.ly/SE-insightsJob Opportunities: http://spr.ly/SE-CareersLinkedIn: https://www.linkedin.com/company/schneider-electricFacebook: https://www.facebook.com/SchneiderElectricTwitter: https://twitter.com/SchneiderElecInstagram: https://instagram.com/schneiderelectric After power was restored, and I powered on the UPS, after about 5 minutes I got the warning message. After power up, all was good on the UPS, and I brought connected equipment back on-line. The UPS battery is weak due to a recent outage or is near the end of its service life. rev2023.3.3.43278. What does a single audible signal every 30 seconds mean coming from the APC BackUPS BE550G-GR? By clicking Accept all cookies, you agree Stack Exchange can store cookies on your device and disclose information in accordance with our Cookie Policy. When I turned the device on it was beeping and giving a flashy red light at the most right icon of the control panel. Schneider Electric support forum for our Data Center and Business Power UPS, UPS Accessories, Software, Services, and associated commercial products designed to share knowledge, installation, and configuration. Grer vos sites, vos produits et vos contacts au niveau des produitsDellEMC laide de la rubrique Gestion des informations de lentreprise. Do roots of these polynomials approach the negative of the Euler-Mascheroni constant? We have a mixture of APC SMART UPS that have been in storage for about 1-2 years. How to notate a grace note at the start of a bar with lilypond? @Xen2050 In many cases, eye and throat irritation occur very quickly, but that may not be sufficient warning to avoid injury. Replacez la batterie dans le compartiment et rinstallez le capot. Load on the UPS is approximately 36%, as reported by front panel. Vous trouverez ici les tapes de connexion de la batterie. Find the genuine APC Replacement Battery for your UPS. Why did Ukraine abstain from the UNHRC vote on China? Batteries require recharging after extended outages and wear out faster when put into service often or when operated at elevated temperatures. Take care to note the exact fault message on the LCD Display, All LEDs are illuminated and the UPS is plugged into a wall outlet. Whats the grammar of «For those whose stories they are»? Did this satellite streak past the Hubble Space Telescope so close that it was out of focus? After keeping aUPS in storage for 1-2 years,you can still recharge the UPS and its batteries but you’ll likely see a significant drop off in length runtime. An APC battery backup device is designed to protect your electronic devices against power surges and failures. Plugged the power in and system returned to normal. APC Battery Backup Instructions. Enjoy! Batteries typically last 3-5 years, however . Four Beeps Every 30 Seconds Back-UPS is running on battery. And schedule another battery replacement in 2022. (BTW, if you look closely at UPS packaging, you’ll usually see a small label with a «recharge by» date on it so that’s something to check when you get a new UPS if you’re not going to install it right away.) All 4 batteries were deformed by heat/gas when we opened the case. Connect and share knowledge within a single location that is structured and easy to search. Please ensure you are using a modern browser, also check your security settings. Now the display says «Connect Battery». C’mon APC, you should have way better smarts in these things to tell us end users what the issue is. Lumping the two questions together could confuse readers. 2021-06-29 Posted: The EcoStruxure IT SmartConnect cloud service provides remote power monitoring, customizable email notifications, remote diagnostics, and UPS firmware updates as part of a Standard Plan for Smart-UPS under product warranty. How to match a specific column position till the end of line? Enjoy! Ask Question Asked 7 years, 8 months ago. For more details, please read our If you receive a APC UPS which does not function, please make sure the battery is connected. I had to remove the machine from the domain Before doing that . Send a co-worker an invite to the Exchange portal. Also checked the internal battery connector for any corrosion or loose connections. Wind Gusts 24 mph. What is the lifespan of an typical UPS battery? Connexion de la batterie sur un nouvel onduleur APC avant utilisation. APC next-generation Smart-UPS are cloud enabled with a built-in SmartConnect Ethernet port. The new Advanced Plan introduces remote reboot; which enables remote power cycling of IT equipment connected to UPS outlet groups and eliminates sending someone on site . @BigHomie: This is a special case. You need to hear this. Is carpet, or another floor covering, appropriate for a server room? Turn on the UPS again and connect a computer with Windows 95/98/ME, Windows NT 4.0 or Win 2000, which runs on Hyperterminal using one of the cables mentioned under the requirements. It only takes a minute to sign up. Powered back up connected equipment; UPS ran for about 5 minutes, then started beeping and displaying «Warning State: Connect Battery». By accepting all cookies, you agree to our use of cookies to deliver and maintain our services and site, improve the quality of Reddit, personalize Reddit content and advertising, and measure the effectiveness of advertising. H2S is so toxic that even a couple of breaths can produce very serious injury, or even death. None. Our next-generation Smart-UPS support remote monitoring on a secure web portal, so you can stay up-to-date on the status of your power infrastructure. How to notate a grace note at the start of a bar with lilypond? You can subscribe to this forum after you log in or create your free account. The connected UPS is an APC SmartUPS 1500 model DLA1500 (the Dell equivalent of an SUA1500). Also, try navigating to the URL of the other unit. You do not have permission to remove this product association. Self test will not run as it is saying connect battery. With next-generation Smart-UPS set up for notifications, power is one less thing I have to worry about, I know I am covered. The dedicated SmartConnect Ethernet Port makes set up easy; it requires no additional hardware or software. 2. and our Bulk update symbol size units from mm to map units in rule-based symbology. Cookie Notice Tutorial for troubleshooting the red Replace Battery LED when illuminated on SMT Series APC Smart-UPS systems. Your daily dose of tech news, in brief. Use a Philips head screwdriver to unscrew the top two screws and fold down the metal cover. I have the APC SMX750i with same problem as You explained: during the day several times it shows battery disconnected and battery connected. Learn more about Stack Overflow the company, and our products. Get monthly updates from Schneider Electric delivered right to your inbox. 04:48 AM, This reply was originally posted by Liam on APC forums on 2/11/2020. Serviceability — Predicitive failure notification Provides early-warning fault analysis ensuring proactive component replacement. So — unit is okay now (until the next time it thinks no battery is connected). Step 1: Power Off And Unplug. APC «Battery Disconnected» May Mean Overheating. The option to replace the entire unit is yours. I’d ponder if they shouldn’t have temp probes on the battery packs and monitor the rise during charging. I have an APC Smart-UPS X 1500V which I just connected to a power source. Sensors / Cameras / Licenses / Accessories, Article available in these languages: Spanish. Can Martian regolith be easily melted with microwaves? The battery red light started flashing and the display indicates connect battery. I’m trying to determine whether I’ve got a bad unit, bad battery (doubtful, since it carries a load fine), or something else going on. The battery I removed has a voltage of about 13v on each battery. For more details, please view our Security Strategy page. You have entered an invalid email address. I realized I messed up when I went to rejoin the domain
I have no time to actively monitor all the equipment we have. Then I opened it to see if there are components that are burned or leak but nothing. Disconnected the isolator plug on the back before they were packed away. . Mutually exclusive execution using std::atomic? APC describes it as the «Replace Battery» indicator. My code is GPL licensed, can I issue a license to have my code be distributed in a specific MIT licensed project? Backup unit is running on battery. Posted: How old is the SMTand have the batteries ever been replaced? . Reddit and its partners use cookies and similar technologies to provide you with a better experience. Sensors / Cameras / Licenses / Accessories. Finally about 1am just went home, and left the unit alone. Something is burning in the server room; how can I quickly identify what it is? The latest incident occurred at about 10pm, with no change in environment (no power drops, etc.). Is a PhD visitor considered as a visiting scholar? Allow the battery to recharge for at least four hours. If so, how close was it? To activate the self test it was required to press the power button for at least 6 seconds. Wiring faults detected include missing ground, hot-neutral, polarity reversal, and overloaded neutral circuit. The estimated runtime is the number of minutes the connected devices (load) can be supported by the UPS battery in the event . Do not attempt to use the UPS. Volt meter show that batteries are ok and fully chared. And as You sad when that happens, unplug the power cord it is still running and put the power cord back UPS is up and running, battery connected. The connect battery indicator would mean that the unit is not seeing appropriate voltage on the battery connector. . Did you also just purchase it? 4. just looking for info re error, don’t particular;y want to buy new batteries and have it turn out to be the board.. at that point have to buy a new UPS anyway, This reply was originally posted by Bill on APC forums on 7/26/2016. Get answers you need by browsing topic-related Frequently Asked Questions (FAQ). The UPS displays a site wiring fault message. Weve made it as easy and cost effective as possible to monitor your UPS online. If the Replace Battery LED remains lit, the battery needs to be replaced. 3. I decided to let MS install the 22H2 build. It has also been emitting a low beep. have You found the solution for this problem? Severity. I added a «LocalAdmin» — but didn’t set the type to admin. APCs next-generation Smart-UPS enables you to monitor your power infrastructure online, anytime — anywhere — from our secure web portal.

Понравилась статья? Поделить с друзьями:
  • Apc c1500 ошибка p 06
  • Andrsserv exe системная ошибка
  • Antipollution перевод на русский язык ошибка пежо 308
  • Apc back ups pro 900 ошибка f06
  • Anthem ошибка подключения к серверу